2                                                                                                                                                                                                                  IMCB02-E5

1

(

*

)

(

*

)

100

30

92

CB500

1    : Rubber packing (option)
This instrument corresponds to a panel thickness of 1 to 10 mm.

9.2

48

96

8.2

(Unit : mm)

Panel cutout

44.

8

91.

8

110

.8

+0

.6 0

25

45

+0.8

0

Mounting bracket

Mounting bracket

CB900

2.2 Dimensions

2.3 Mounting procedures

(1) Make a rectangular holes corresponding to the number of

instruments to be mounted through the panel by referring to

the panel cutout dimensions.

(2) Insert the instrument into the panel from the panel cutout.

(3) Insert the mounting bracket into the mounting groove of the

instrument.(Fig.1)

(4) Push the mounting bracket into the instrument until the

instrument is firmly fixed to the panel.(Fig.2)

            *After inserting the CB900 in the panel, fix it to
       the panel rear surface with the two mounting
       brackets so that the upper and lower mounting
       brackets are positioned diagonally.

   

!"

The front of the instrument of the waterproof and dustproof construction type (CB900: mounting bracket 4 pieces) conforms to

IP65

 with the instrument mounted on the control panel. In order to assure the waterproof and dustproof properties, check that

there is no dislocation of the packing nor clearance between the instrument and mounting frame with the instrument mounted.

!"

If the packing is damaged, contact your nearest RKC agent or our sales office.

!"

The instrument can also be mounted by tightening screws. Insert a hexagon nut in the mounting bracket according to the above

procedure (Fig. 3) to mount the bracket, then fix the instrument with the screw. Use the hexagon nuts and screws attached.

!"

CB900 is used in the above figures for explanation, but the same mounting procedures also apply to CB400/CB500/CB700.

3. WIRING

3.1 Wiring cautions

9.2

8.2

1

100

(Unit : mm)

48

Panel cutout

25

45

+0

.8 0

+0.6

0

92

30

96

110.

8

91.

8

44.

8

1    : Rubber packing (option)
This instrument corresponds to a panel thickness of 1 to 10 mm.

CB400

(

*

)

(

*

)

1

CB700

(Unit : mm)

Panel cutout

86

.8

67

.8

67

.8

72

9.2

100

8.2

25

68

+0.7

0

72

30

68

+0

.7 0

1    : Rubber packing (option)
This instrument corresponds to a panel thickness of 1 to 10 mm.

(

*

)

(

*

)

1

CB900

(Unit : mm)

Panel cutout

100

8.2

96

9.2

25

92

+0.8

0

(

*

2)

(

*

1)

91.

8

91.

8

110

.8

96

30

92

+0

.8 0

*2: Up to 4 mounting brackets can be used.

*1: Rubber packing (option)
This instrument corresponds to a panel thickness of 1 to 10 mm.

• 

Install the noise filter on the panel which is always grounded

and minimize the wiring distance between the noise filter

output side and the instrument power terminals.

NOTES

(1) For thermocouple input, use the specified compensation wire.

(2) For RTD input, use leads with low resistance and having no

resistance differences among the 3 leads.

(3) Conduct input signal wiring away from instrument power,

electric equipment power and load lines to avoid noise

induction.

(4) Conduct instrument power wiring so as not to be influenced by

noise from the electric equipment power. If the instrument may

be affected by external noise, a noise filter should be used.

• 

Shorten the distance between twisted power supply wire

pitches. The shorter the distance between the pitches, the

more effective for noise reduction.

• 

Do not install fuses and/or switches on the filter output signal

since this may lessen filter effect.

Fig.1

Mounting bracket

OUT

Minimize

Instrument

IN

Twist these leadwires

Shorten distance between

Instrument power

Noise filter

terminals

distance

power

pitches

When mounting the instrument by tightening

screw

Insert the L-shaped hook

of the mounting bracket

into the groove, then firmly

secure it in the groove.

Fig.3

When tightening each

screw, tighten it only one

turn just after it touches

the panel.

3

2

Hexagon nut

Mounting bracket

1

Fig.2

Содержание CB400 Series

Страница 1: ...lowing damage which the user or third party may suffer Damage incurred as a result of using this product Damage caused by product failure which cannot be predicted by RKC Other indirect damage In orde...

Страница 2: ...mm 48 Panel cutout 25 45 0 8 0 0 6 0 92 30 96 110 8 91 8 44 8 1 Rubber packing option This instrument corresponds to a panel thickness of 1 to 10 mm CB400 1 CB700 Unit mm Panel cutout 86 8 67 8 67 8...

Страница 3: ...A Resistive load Control output rated Relay contact output 250 V AC 3A Resistive load Voltage pulse output 0 12 V DC Load resistance 600 or more Current output 4 to 20 mA DC Load resistance 600 or les...

Страница 4: ...LM2 R S CB500 PV SV SET C C C C 1 2 4 5 6 7 3 AT OUT1 OUT2 ALM1 ALM2 SET R S CB400 PV SV C C C C Measured value PV display unit Green Displays measured value PV Displays various parameter symbols depe...

Страница 5: ...s the self tuning ON OFF 0 Proportional band P Temperature input 1 0 1 to span or 9999 999 9 C F Voltage current inputs 1 to 100 0 of span Set when PI PD or PID control is performed For heat cool PID...

Страница 6: ...e the LBA setting time 3 Relay contact output 20 sec Voltage pulse output Trigger output for triac driving Triac output 2 sec 4 Relay contact output 20 sec Voltage pulse output Triac output 2 sec 5 De...

Страница 7: ...h value to match the controlled object 6 4 Self tuning ST function The ST function is used to automatically calculate and set adaptive PID constants anytime when the power is turned on the SV is chang...

Страница 8: ...06 to 0 0 50 0 07 to 0 0 100 0 08 to 0 0 200 0 09 to 0 0 300 0 10 to 0 0 500 0 P P P P P 0 to 5 V DC 1 to 5 V DC 0 to 20 mA DC 4 to 20 mA DC 01 01 01 01 4 6 7 8 to 0 0 100 0 Pt100 JPt100 1 0 to 399 0...

Отзывы: