background image

6                                                                                                                                                                                                                  IMCB02-E5

#1:Factory set value

Symbol

Name

Setting range

Description

#1

 Cool-side

 proportioning

 cycle  ( t )

  1 to 100 sec (0 can not be set.)

  *Not displayed if the control

output is current output.

  Set control cool-side output cycle for

  heat/cool PID action.

        See *4.

  PV bias (Pb)

  Temperature input:

  -1999 to +9999 

°

C[

°

F ] or

  -199.9 to +999.9 

°

C [

°

F ]

 Voltage/current inputs:

  -span to +span

  Sensor correction is made by adding

  bias value to measured value (PV).

        0 or 0.0

  Set data lock

 function (LCK)

  See *5.

  Performs set data change

 enable/disable.

          0000

*1: Precautions for heater break alarm (HBA) setting

,#

Displayed only for when HBA is selected as second alarm.

,#

HBA is not available on a current output.

,#

Set HBA set value to a value about 85 % of current transformer input value (CT).    However, when power supply variations are

large, set the HBA to a slightly smaller value.    In addition, when two or more heaters are connected in parallel, set the HBA to a

slightly larger value so that it is activated even with only one heater is broken (However, within the value of CT).

,#

When the HBA set value is set to "0.0" or the current transformer is not connected, the HBA is turned on.

*2: Precautions for control loop break alarm (LBA) setting

,#

Displayed only for when LBA is selected as first alarm or second alarm.

,#

Usually set the set value of the LBA to a value twice the integral time (I).

,#

No control loop break alarm can be used at heat/cool PID control action.

,#

No LBA function is activated while the AT function is activated.

,#

The LBA function is activated only at the 0 % or 100 % of PID computed value. Therefore, the time from trouble occurrence till the

activation of the LBA function equals the time until the PID computed value becomes 0 % or 100 % plus the LBA setting time.

,#

If LBA setting time is too short or does not match the controlled object, the LBA may be turned on and off or not be turned on. In

this case, depending on the situation, change the LBA setting time.

*3:

 Relay contact output : 20 sec, Voltage pulse output/Trigger output for triac driving/Triac output : 2 sec

*4:

 Relay contact output : 20 sec,    Voltage pulse output/Triac output : 2 sec

*5: Details of set data lock level selection

Setting

                        Details of lock level

Setting

                        Details of lock level

0000

SV and parameter can be set.

0011

Only SV can be set.

0001

Only SV and alarms (ALM1, ALM2) can be set.

0101

Only alarms (ALM1, ALM2) can be set.

0010

Only setting items other than alarms

(ALM1, ALM2) can be set.

0110

Only setting items other than SV and alarms (ALM1,

ALM2) can be set.

0100

Only setting items other than SV can be set.

0111

SV and parameter cannot be set.

,#

Each locked setting item can only be monitored.

,#

Each alarm setting item [HBA, LBA, LBD] can be locked when any of "0001," "0011," "0101" and "0111" is set.

5.3  Parameter setting procedure

"#

Setting set value (SV)

              Example: Following is an example of set value (SV) to 200 

°

C

"#

Setting parameters other than set value (SV)

The setting procedures are the same as those of example (2) to (4) in the above "

"

Setting set value (SV).

"  Pressing the 

SET

 key

after the setting end shifts to the next parameter. When no parameter setting is required, return the instrument to the PV/SV display

mode.

NOTE

                                                                                                   

Key operational cautions

,#

Even if the displayed value is changed, it is not registered.    To register it, press the 

SET

 key.

,#

If the key is not operated for more than 1 minute, the present mode returns to the PV/SV display mode.

Some parameter symbols may not be displayed depending on the specification.

SV

PV

(1) Set to the SV setting mode

(2) Shift of the digit brightly lit

(3) Numeric value change

(4) Set value entry

up to the hundreds digit.

Press the 

<R/S

 key to shift

the digit which lights brightly

SV

PV

SV

PV

SV

PV

Press the 

SET

 key to enter

the SV setting mode.

The digit which light brightly

is settable.

Press the 

UP

 key to set "2."

Pressing the 

UP

 key

increase numerals, and

pressing the 

DOWN

 key

decrease numerals.

After finishing the setting,

press the 

SET

 key. All of

the set value digits light

brightly and as a result

the instrument returns to

the PV/SV display mode.

Содержание CB400 Series

Страница 1: ...lowing damage which the user or third party may suffer Damage incurred as a result of using this product Damage caused by product failure which cannot be predicted by RKC Other indirect damage In orde...

Страница 2: ...mm 48 Panel cutout 25 45 0 8 0 0 6 0 92 30 96 110 8 91 8 44 8 1 Rubber packing option This instrument corresponds to a panel thickness of 1 to 10 mm CB400 1 CB700 Unit mm Panel cutout 86 8 67 8 67 8...

Страница 3: ...A Resistive load Control output rated Relay contact output 250 V AC 3A Resistive load Voltage pulse output 0 12 V DC Load resistance 600 or more Current output 4 to 20 mA DC Load resistance 600 or les...

Страница 4: ...LM2 R S CB500 PV SV SET C C C C 1 2 4 5 6 7 3 AT OUT1 OUT2 ALM1 ALM2 SET R S CB400 PV SV C C C C Measured value PV display unit Green Displays measured value PV Displays various parameter symbols depe...

Страница 5: ...s the self tuning ON OFF 0 Proportional band P Temperature input 1 0 1 to span or 9999 999 9 C F Voltage current inputs 1 to 100 0 of span Set when PI PD or PID control is performed For heat cool PID...

Страница 6: ...e the LBA setting time 3 Relay contact output 20 sec Voltage pulse output Trigger output for triac driving Triac output 2 sec 4 Relay contact output 20 sec Voltage pulse output Triac output 2 sec 5 De...

Страница 7: ...h value to match the controlled object 6 4 Self tuning ST function The ST function is used to automatically calculate and set adaptive PID constants anytime when the power is turned on the SV is chang...

Страница 8: ...06 to 0 0 50 0 07 to 0 0 100 0 08 to 0 0 200 0 09 to 0 0 300 0 10 to 0 0 500 0 P P P P P 0 to 5 V DC 1 to 5 V DC 0 to 20 mA DC 4 to 20 mA DC 01 01 01 01 4 6 7 8 to 0 0 100 0 Pt100 JPt100 1 0 to 399 0...

Отзывы: