Temperature Controller Driver
GP-Pro EX Device/PLC Connection Manual
237
6.7
SA Series
This address can be specified as system data area.
<Communication identifier list>
Device
Bit Address
Word Address
32
bits
Notes
Communication identifier
0000.0-001E.F
0000-001E
*1
*2
*1
There are cases for which writing is not available depending on the device address. Check the
identifying attributes of the external device’s manual before use.
*2
When bit is written, the indicator reads the corresponding word address of external device, assign
a bit to the read word address, and return to the external device. There are cases when correct data
cannot be written if the word address is written using a ladder program, while the indicator reads
data of the external device and sends it back.
Address
Identifier
Description
00
M1
Measured value(PV)
01
B1
Burnout
02
AA
Alarm 1 status
03
AB
Alarm 2 status
04
O1
Heat-side manipulated output value
05
O2
Cool-side manipulated output value
06
ER
Error code
07
SR
RUN/STOP function
08
G1
Autotuning
09
G2
Self-tuning
0A
S1
Set value (SV)
0B
A1
Alarm 1 set value
0C
A2
Alarm 2 set value
0D
A5
Control loop break alarm
0E
A6
Control loop break alarm deadband
0F
P1
Heat-side proportional band (P)
10
I1
Integral time (I)
11
D1
Derivative time (D)
12
W1
Anti-reset windup
13
T0
Heat-side proportioning cycle time
14
P2
Cool-side proportional band
15
V1
Overlap/deadband
16
T1
Cool-side proportioning cycle time
17
PB
PV bias
18
F1
Digital filter
19
LK
Set data lock function
1A
EB
EEPROM storage mode
1B
EM
EEPROM storage status
1C
LA
Analog output specification selection
1D
HV
Analog output scale high
1E
HW
Analog output scale low