MOTOR BRACKET

ATTACHMENT OF MOTOR BRACKET

The motor bracket attaches to the extension
tube with (2) ½" x 4½" long – grade 8 bolts,
washers and lock nuts.  Position the motor
bracket so that one angle is on each side of the
extension tube.  The bolts can be inserted
through the holes in the angles at the top of the
motor bracket and through the extension tube
and back through the second angle.  Tighten
both lock nuts securely. When an extended
down tube is used, the smaller square tubing
(3" x 3") will telescope inside the larger square
tubing (3.5" x 3.5") The brackets on the top of
the motor bracket are bolted in slots to allow
the larger tube to bolt to the top of the motor.
The 3" x 3" tube should always bolt to the
ceiling bracket.
If the fan assembly is mounted directly to the
ceiling bracket without an extension tube, you
will need to purchase (4) ½" x ½" grade 8 bolts
locally to bolt the brackets together properfspy.

SAFETY CABLES

Cables are included with this kit to wrap
around the bolted brackets at the ceiling and
the top of the extension tube.  A second
cable should be wrapped through the bottom
of the extension tube and through the top of
the motor housing. When installing with
adjustable length extension tubes, a third
cable should be used to secure the center
bolted joint of the extension tubes. These
cables support the fan to the ceiling if one of
the bolted joints were to come loose.
Secure the cables with the cable clamps that
are provided.  See figures to the right.

I M P O R TA N T ! ! !

8

Pub. No. RFSP Rev. 5 - December 2010 

REVOLUTION SP FAN 

Содержание REVOLUTION SP

Страница 1: ...INSTALLATION AND OWNER S MANUAL PRINTED IN U S A PUBLICATION NO RFSP REV 5 RITE HITE PRINT SHOP DECEMBER 2010 This Manual Covers All Fans Shipped 1 07 to Date...

Страница 2: ...the Planned Maintenance Program P M P which can be fitted to your specific operation Call your local representative or RITE HITE at 1 414 355 2600 or toll free at 1 800 456 0600 The RITE HITE product...

Страница 3: ...ing the work area the power supply has been locked in the OFF position or disconnected It is mandatory that an approved lockout device is utilized An example of a lockout device is illustrated above T...

Страница 4: ...ave received all of the above items before installation begins Notify the factory if parts are missing or damaged TOOLS REQUIRED 2 7 16 wrenches 2 wrenches 1 1 box end wrench 1 1 1 16 box end wrench 2...

Страница 5: ...reas when the fan is running Whenever possible allow 12 additional clearance to IMPORTANT If the ceiling support structure is an open web design all hanging dimensions can be taken from the underside...

Страница 6: ...Use a level to ensure the extension tube is hanging vertical CEILING TRUSS MOUNTING STRUCTURAL ANGLES Never mount the fan to only one building joist One joist will not provide the rigidity and suppor...

Страница 7: ...plied by Rite Hite is designed to make the installation of the kit easier The two formed angles span existing building trusses The drawing below shows how the brackets are used to secure the angles to...

Страница 8: ...e 3 x 3 tube should always bolt to the ceiling bracket If the fan assembly is mounted directly to the ceiling bracket without an extension tube you will need to purchase 4 x grade 8 bolts locally to b...

Страница 9: ...r object For the most support possible attach the cables to the ceiling at 90 degrees to each other and as far away from the point where the fan is mounted as possible These cables are secured at the...

Страница 10: ...to 75 ft lb 102 NM Clean each blade with a paper towel to remove fingerprints and dirt before the blades are installed In the event a blade is damaged the damaged blade and the blade opposite must be...

Страница 11: ...o open the relay will stop the fan REMOTE STOP FOR OPEN AIR ENVIRONMENT When fans are used in open air environments it may be necessary to shut the fans down as wind speed increases These controls can...

Страница 12: ...or another controller MAY NOT share the same conduit The conduit with the incoming power and the conduit with the power going to the motor should be separated by a minumun of 6 152 mm Do not use soli...

Страница 13: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 13 CONTROL BOX WIRING...

Страница 14: ...REVOLUTION SP FAN 14 Pub No RFSP Rev 5 December 2010 STOP CURCUIT FOR MULTIPLE FANS SCHNEIDER ELECTRIC...

Страница 15: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 15 REMOTE MOUNTED FAN FOR SCHNEIDER ELECTRIC...

Страница 16: ...omer RECOMMENDED FUSE RATINGS Recommended Branch Recommended Circuit Protection Incoming Service Input Voltage Amps Amps 110 120V 1PH 60 Hz 20A 20A 200 240V 1PH 60 Hz 15A 15A 200 240V 3PH 60 Hz 15A 10...

Страница 17: ...the master frequency drive will restart the frquency drive only Cycle the remote on off switch to restart all fans Ceiling mounted standard control boxes should not be mounted inside the fan diameter...

Страница 18: ...IONAL The laminated beam brackets are through bolted with one bracket on each side of the laminated or concrete beam The standard ceiling mounting bracket should then be attached to this bracket in th...

Страница 19: ...n Do not use strong solvents FAN MOUNTING Re torque all fasteners 1 2 13 Grade 8 98 ft lbs 5 16 18 Grade 8 29 ft lbs Check the fan including mounting supports to make sure all hardware is tight and sh...

Страница 20: ...ple will detect It is caused by the frequency drive creating power for the fan motor and it will always be present with a motor that is controlled by a variable frequency drive 3 Wind noise will be pr...

Страница 21: ...switch Check for loose jumper wire between terminals 1 and 11 on frequency drive Stop signal from fire protection system If fan is wired to shut off with fire protection system verify that fan is not...

Страница 22: ...6100 mm 29 rpm 16 fan 4880 mm 35 rpm 12 fan 3660 mm 50 rpm 8 fan 2440 mm 75 rpm If the fan rotates at a different speed than above check the gearbox label to insure the wrong size blades were not ins...

Страница 23: ...ket Assembly includes the following parts White 135144 1 Ceiling Mount Bracket White 135145 2 Spacer White 135146 2 Clamp Plate White 125338 4 Bolt 5 13 x 2 Grade 8 125339 6 Nut 5 13 Nylock Grade 8 12...

Страница 24: ...ube 135129 2 Top Angle Black 125338 4 Bolt 5 13 x 1 5 Grade 8 125339 6 Nut 5 13 Nylock Grade 8 125340 2 Bolt 5 13 x 4 5 Grade 8 51709 8 Washer 5 Flat 125337 2 Top Angle GREY 4 Bolt 5 13 x 1 5 Grade 8...

Страница 25: ...olished 135160 4 Clevis Cover Painted Dome Hub Cover 135161 1 Dome Hub Cover Painted to match Annodize 135283 1 Dome Hub Cover Painted to match MILL FINISH 135162 1 Dome Hub Cover Plated to match Poli...

Страница 26: ...4 1 1 HP 110 120 V 1 PH 60 Hz 135185 1 1 HP 208 240 V 1 PH 60 Hz 135186 1 1 HP 208 240 V 3 PH 60 Hz 135187 1 1 HP 460 480 V 3 PH 60 Hz 135188 1 1 HP 575 V 3 PH 60 Hz 135189 1 1 HP 208 240 V 1 PH 50 Hz...

Страница 27: ...5 stabilization cable attachment white 125368 5 Bolt 5 13 x 5 0 Grade 8 125339 5 Nut 5 13 Nylock Grade 8 51709 6 Washer 5 Flat 125365 1 4 7 Down Tube Assembly Includes the following parts grey 125366...

Страница 28: ...st Fan includes the following parts white 135269 2 Angle 4 625 x 3 x 1875 x 120 white 2 Bolt 5 13 x 10 fully threaded grade 8 51709 4 Washer 5 Flat 125339 2 Nut 5 13 Nylock Grade 8 135270 2 Bracket Sp...

Страница 29: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 29 NOTES...

Страница 30: ...REVOLUTION SP FAN 30 Pub No RFSP Rev 5 December 2010 NOTES...

Страница 31: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 31 NOTES...

Страница 32: ...HITE exclusive warranty RITE HITE EXPRESSLY DISCLAIMS ALL IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS Non standard RITE HITE warranties if any must be specified...

Отзывы: