REVOLUTION SP FAN

ANNUAL PLANNED MAINTENANCE

RUN / TEST

Turn the power disconnect switch on the
control box to the ON position.  Allow a few
seconds for the frequency drive to power up.  

Turn the Fan Control to the ON position.
Watch the rotation of the fan.  The fan should
turn clockwise when you are standing below
the fan looking up.  If the rotation is the wrong
direction, disconnect power to the control box
and reverse two of the three wires from the
control box to the motor.

Adjust the fan speed to 30 hz. Count the
number of revolutions the fan makes in 
1 minute. They should be approximately the
following:

12’ (2440 mm)  Fans = 40 rpm
10’ (3050 mm)  Fans = 50 rpm

8’ (3660 mm)  Fans = 60 rpm

If the fans do not spin at these speeds, consult
factory for assistance.

FAN BLADE CLEANING

•  Dirt and dust may be removed from the

blades by using a cloth or soft non-metallic
brush.

•  Stubborn stains may be removed with a

cloth dampened with a mild detergent
solution. Do not use strong solvents.

FAN MOUNTING:

•  Re-torque all fasteners [1/2-13 Grade 8 (98

ft-lbs)], [5/16-18 Grade 8 (29 ft-lbs)].

•  Check the fan, including mounting supports

to make sure all hardware is tight and
shows no wear and tear.

CABLES:

•  Re - Torque clamps.

•  Check for fraying or wear.

GEAR REDUCER:

•  Check for oil leaks.  If leaks are present,

contact factory.  

•  Check oil level.  The oil type is marked on

the gear case.  Add oil if necessary.

MOTOR:

•  Check motor for accumulated dust and dirt.

Remove using a brush or compressed air.

FAN CONTROLLER:

•  Examine all terminal connections inside the

control box, tighten any loose connections.

•  Use compressed air at 90~100 psi, to blow

loose debris and dust out of controller
interior. 

When cleaning or attempting to re-torque you
must unplug or disconnect the fan and
controller from the power supply.

WA R N I N G ! ! !

!

LOSS OF POWER
Both the disconnect and the ON/OFF
switches must be turned to the OFF
positions to restart the fan. Turn the
disconnect switch to the ON position.
Wait 5 seconds for the variable frequency
drive to power up before turning the fan
switch to the ON position.

I M P O R TA N T ! ! !

Pub. No. RFSP Rev. 5 - December 2010   

19

Содержание REVOLUTION SP

Страница 1: ...INSTALLATION AND OWNER S MANUAL PRINTED IN U S A PUBLICATION NO RFSP REV 5 RITE HITE PRINT SHOP DECEMBER 2010 This Manual Covers All Fans Shipped 1 07 to Date...

Страница 2: ...the Planned Maintenance Program P M P which can be fitted to your specific operation Call your local representative or RITE HITE at 1 414 355 2600 or toll free at 1 800 456 0600 The RITE HITE product...

Страница 3: ...ing the work area the power supply has been locked in the OFF position or disconnected It is mandatory that an approved lockout device is utilized An example of a lockout device is illustrated above T...

Страница 4: ...ave received all of the above items before installation begins Notify the factory if parts are missing or damaged TOOLS REQUIRED 2 7 16 wrenches 2 wrenches 1 1 box end wrench 1 1 1 16 box end wrench 2...

Страница 5: ...reas when the fan is running Whenever possible allow 12 additional clearance to IMPORTANT If the ceiling support structure is an open web design all hanging dimensions can be taken from the underside...

Страница 6: ...Use a level to ensure the extension tube is hanging vertical CEILING TRUSS MOUNTING STRUCTURAL ANGLES Never mount the fan to only one building joist One joist will not provide the rigidity and suppor...

Страница 7: ...plied by Rite Hite is designed to make the installation of the kit easier The two formed angles span existing building trusses The drawing below shows how the brackets are used to secure the angles to...

Страница 8: ...e 3 x 3 tube should always bolt to the ceiling bracket If the fan assembly is mounted directly to the ceiling bracket without an extension tube you will need to purchase 4 x grade 8 bolts locally to b...

Страница 9: ...r object For the most support possible attach the cables to the ceiling at 90 degrees to each other and as far away from the point where the fan is mounted as possible These cables are secured at the...

Страница 10: ...to 75 ft lb 102 NM Clean each blade with a paper towel to remove fingerprints and dirt before the blades are installed In the event a blade is damaged the damaged blade and the blade opposite must be...

Страница 11: ...o open the relay will stop the fan REMOTE STOP FOR OPEN AIR ENVIRONMENT When fans are used in open air environments it may be necessary to shut the fans down as wind speed increases These controls can...

Страница 12: ...or another controller MAY NOT share the same conduit The conduit with the incoming power and the conduit with the power going to the motor should be separated by a minumun of 6 152 mm Do not use soli...

Страница 13: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 13 CONTROL BOX WIRING...

Страница 14: ...REVOLUTION SP FAN 14 Pub No RFSP Rev 5 December 2010 STOP CURCUIT FOR MULTIPLE FANS SCHNEIDER ELECTRIC...

Страница 15: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 15 REMOTE MOUNTED FAN FOR SCHNEIDER ELECTRIC...

Страница 16: ...omer RECOMMENDED FUSE RATINGS Recommended Branch Recommended Circuit Protection Incoming Service Input Voltage Amps Amps 110 120V 1PH 60 Hz 20A 20A 200 240V 1PH 60 Hz 15A 15A 200 240V 3PH 60 Hz 15A 10...

Страница 17: ...the master frequency drive will restart the frquency drive only Cycle the remote on off switch to restart all fans Ceiling mounted standard control boxes should not be mounted inside the fan diameter...

Страница 18: ...IONAL The laminated beam brackets are through bolted with one bracket on each side of the laminated or concrete beam The standard ceiling mounting bracket should then be attached to this bracket in th...

Страница 19: ...n Do not use strong solvents FAN MOUNTING Re torque all fasteners 1 2 13 Grade 8 98 ft lbs 5 16 18 Grade 8 29 ft lbs Check the fan including mounting supports to make sure all hardware is tight and sh...

Страница 20: ...ple will detect It is caused by the frequency drive creating power for the fan motor and it will always be present with a motor that is controlled by a variable frequency drive 3 Wind noise will be pr...

Страница 21: ...switch Check for loose jumper wire between terminals 1 and 11 on frequency drive Stop signal from fire protection system If fan is wired to shut off with fire protection system verify that fan is not...

Страница 22: ...6100 mm 29 rpm 16 fan 4880 mm 35 rpm 12 fan 3660 mm 50 rpm 8 fan 2440 mm 75 rpm If the fan rotates at a different speed than above check the gearbox label to insure the wrong size blades were not ins...

Страница 23: ...ket Assembly includes the following parts White 135144 1 Ceiling Mount Bracket White 135145 2 Spacer White 135146 2 Clamp Plate White 125338 4 Bolt 5 13 x 2 Grade 8 125339 6 Nut 5 13 Nylock Grade 8 12...

Страница 24: ...ube 135129 2 Top Angle Black 125338 4 Bolt 5 13 x 1 5 Grade 8 125339 6 Nut 5 13 Nylock Grade 8 125340 2 Bolt 5 13 x 4 5 Grade 8 51709 8 Washer 5 Flat 125337 2 Top Angle GREY 4 Bolt 5 13 x 1 5 Grade 8...

Страница 25: ...olished 135160 4 Clevis Cover Painted Dome Hub Cover 135161 1 Dome Hub Cover Painted to match Annodize 135283 1 Dome Hub Cover Painted to match MILL FINISH 135162 1 Dome Hub Cover Plated to match Poli...

Страница 26: ...4 1 1 HP 110 120 V 1 PH 60 Hz 135185 1 1 HP 208 240 V 1 PH 60 Hz 135186 1 1 HP 208 240 V 3 PH 60 Hz 135187 1 1 HP 460 480 V 3 PH 60 Hz 135188 1 1 HP 575 V 3 PH 60 Hz 135189 1 1 HP 208 240 V 1 PH 50 Hz...

Страница 27: ...5 stabilization cable attachment white 125368 5 Bolt 5 13 x 5 0 Grade 8 125339 5 Nut 5 13 Nylock Grade 8 51709 6 Washer 5 Flat 125365 1 4 7 Down Tube Assembly Includes the following parts grey 125366...

Страница 28: ...st Fan includes the following parts white 135269 2 Angle 4 625 x 3 x 1875 x 120 white 2 Bolt 5 13 x 10 fully threaded grade 8 51709 4 Washer 5 Flat 125339 2 Nut 5 13 Nylock Grade 8 135270 2 Bracket Sp...

Страница 29: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 29 NOTES...

Страница 30: ...REVOLUTION SP FAN 30 Pub No RFSP Rev 5 December 2010 NOTES...

Страница 31: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 31 NOTES...

Страница 32: ...HITE exclusive warranty RITE HITE EXPRESSLY DISCLAIMS ALL IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS Non standard RITE HITE warranties if any must be specified...

Отзывы: