MOTOR WIRING
The fan motor will receive three phase power
from the fan control box even if single phase
power is provided to the control box. Remove
the cover from the motor junction box. Change
the wire leads as necessary for high or low
voltage. See the diagrams on this page below
for the appropriate wiring.
CONDUIT RESTRICTIONS
AC supply lines for a controller
MAY
share the same conduit with AC supply
lines for one or more additional
controllers.
AC supply lines for a controller and
output / motor leads for the same
controller or another controller
MAY NOT
share the same conduit.
The conduit with the incoming power and the
conduit with the power going to the motor
should be separated by a minumun of 6”(152
mm)
Do not use solid core wiring of any size
or insulation class for controller output /
motor leads.
I M P O R TA N T ! ! !
Use one of the wire types listed below to
connect the fan control box to the motor.
Acceptable unshielded cable types:
THHN / THNW, rated for 600V and
75 deg. to 90 deg. Celsius
Acceptable shielded cable types:
RHH / RHW-2, rated for 600V and 75
deg to 90 deg. Celsius
Belden 29501 through 29507
RHH / RHW-2, tray rated for 600V
and 75 deg. to 90 deg. Celsius
Shawflex 2ACD / 3ACD or
equivalent.
I M P O R TA N T ! ! !
REVOLUTION SP FAN
12
Pub. No. RFSP Rev. 5 - December 2010
Содержание REVOLUTION SP
Страница 13: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 13 CONTROL BOX WIRING...
Страница 14: ...REVOLUTION SP FAN 14 Pub No RFSP Rev 5 December 2010 STOP CURCUIT FOR MULTIPLE FANS SCHNEIDER ELECTRIC...
Страница 15: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 15 REMOTE MOUNTED FAN FOR SCHNEIDER ELECTRIC...
Страница 29: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 29 NOTES...
Страница 30: ...REVOLUTION SP FAN 30 Pub No RFSP Rev 5 December 2010 NOTES...
Страница 31: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 31 NOTES...