Pub. 56560007 Rev. 4 - JUNE 2014
D4
4" Side Frame Widths
1. Reference the standard installation instructions
5656-0007 and 1531-0002 along with these
instructions before proceding.
2. All 4" side frame width blockout must use brackets
to attach blockout to the building wall. This due to
the lack of space between the boards in the
construction of the blockouts.
(Warning: Drilling out a space between the
boards within the blockout, then thru bolting, is
acceptable as long as the strength and integrity
of the blockout is maintained.)
Fastening Methods
Concrete Block or Brick Wall
1. Install fastener into mortar joint if possible. Use 3/8"
x 4" lag screw with expansion shields, 3/8" x 4" one
piece anchor with expansion collar, or equivalent
fastener.
2. Through bolt fastening is required if the mortar joint
will not support the members. Bore a hole through
the building wall. Use a 3/8" dia. threaded rod with
a washer, nut and jam nut on each end - it may be
necessary to install a back-up plate - steel or wood
- when the wall will not support the bolt.
3. Use a minimum of 6 brackets on each side member
assembly.
Concrete Tilt-Up Walls (Precast)
1. Use a 3/8" x 4" lag bolt with expansion shields, 3/8"
x 4" one piece anchor bolts with expansion collar, or
equivalent fastener. If building wall is too thin to
effectively hold the lag bolt or anchor bolt, the
through bolt method of attachment is required.
Metal Side Building
1. Through bolt method of attachment is required for
this building style. It will be necessary to install a
back-up plate that is fastened directly to structural
members when it is not possible to fasten directly to
structural building members. Use a 3/8" diameter
bolt with a washer and lock nut to fasten the unit to
the structural members of the building or to the
back-up plates. If necessary, use a 3/8" diameter
threaded rod with a washer and lock nut on each
end.
Bracketing Details
The side members are furnished with brackets to suit
the application.
1. Position the side members on their marks.
2. Mark the side member for bracket installation. The
brackets should be positioned 12" - 15" from the top
and bottom, and also centered on the side member.
(See Figure 6) For example, line up the mounting
hole on the bracket with a mortar joint on the wall
and attach the mounting bracket to the side
member backer board.
3. Attach the brackets to the side member backer. Use
the supplied 1/4" x 1 1/4" wood screws for wood
backers, or #12 x 3/4" tek-screws for steel backers.
610 SERIES SIDE FRAME
Содержание ELIMINATOR II 610 Series
Страница 12: ...610 SERIES SIDE FRAME D5 Pub 56560007 Rev 4 JUNE 2014 FIGURE 5 FIGURE 6 FIGURE 7...
Страница 27: ...610 C STYLE CURTAIN OPERATION OF PULL ROPES Pub 28610002 Rev 2 JUNE 2014 G4 FIGURE 5...
Страница 38: ...38 Pub ECII 610 Rev 11 September 2015 ELIMINATORTM II COMBOSHELTERTM II 610 SERIES NOTES...
Страница 39: ...Pub ECII 610 Rev 11 September 2015 39 ELIMINATORTM II COMBOSHELTERTM II 610 SERIES NOTES...