6
Figure 8: Unit backside: batteries compartment, tamper and DIP switch
To
configure
the DIP switch:
NOTE:
* = DIP Switch default settings.
1. [For one-way operating mode]: Set the DIP switch 1 to 1-way, and configure either
smoke (2), heat (3) or smoke and heat.
2. [For two-way operating mode]: Set the DIP switch 1 to 2-way, and configure activation
of the Smoke and Heat detectors from the system panel. (In this mode, the DIP switch
2 & 3 settings are irrelevant.)
3. Open the battery compartment cover (see Figure 8).
WARNING:
The detector batteries are supplied inside of the unit, which are covered with
plastic wrapping. Remove the plastic wrapping from the batteries before
installation, and then perform a functional test of the detector according to the
Testing section of these instructions.
4. Observing proper polarity, insert two CR123 3V lithium batteries (supplied) into the
batteries compartment, and then close the compartment cover.
5. For the
Smoke and Heat Detector
to identify itself to the system's receiver, perform
the registration either by entering the
Smoke and Heat Detector
’s 11-digit serial code
number or by the following RF allocation steps:
a. Set the alarm system to learn mode.
b. Remove the battery from the insulation material and reinsert it into the transmitter,
paying attention to the polarity.
c. Send a write message by pressing the tamper switch for at least 3 (or closing the
bracket) seconds until panel recognition is displayed.
WARNING:
This detector is not suitable for installation in a hazardous location, as defined in the national
electrical code. Do not use detector in an outlet controlled by a wall switch.
6. Line up the side slot of the bracket and the detector. Push the detector onto the
mounting bracket and turn it clockwise to secure it into place.
Insert the locking pin in order to secure the mounting bracket to the detector (Figure 7).
7. Pull the detector outward to make sure it is securely attached to the mounting bracket.
DIP Switch
1-1-Way (Off) / 2-Way (On)*
2-Smoke Off / On*
3-Heat Off / On*
*=Default
Tamper
Содержание RWX34S
Страница 1: ...1 2 WAY SMOKE HEAT DETECTOR MODEL RWX34S INSTALLATION INSTRUCTIONS EN FR ES PR IT DE SE ...
Страница 20: ...19 ...