It is recommended that a licensed professional install 
the appliance, inspect it, and leak test it before use.  
The warranty may be voided due to any improper 
installation.

 

The installer should have skills such as:

 

• 

gas sizing

 

• 

connecting gas lines, water lines, valves, 
electricity, 

 

• 

knowledge of applicable national, state, and 
local codes.

 

If you lack these skills contact a licensed professional.

 

Installation Instructions

 

Installation Steps

 

General Instructions

 

 

Prepare for Installation

 ...................................... 

5

 

 

Determine Installation Location

 ......................... 

5

 

 

Checklist to Determine Installation Location

 ..... 

8

 

 

Mount to Wall

 .................................................... 

8

 

 

Remove the Front Panel

 .................................... 

9

 

 

Installation of Plumbing

 ..................................... 

9

 

 

Checklist for Plumbing

 ..................................... 

11

 

 

Installation of Gas Supply

 ................................. 

11

 

 

Connect Electricity

 ........................................... 

13

 

 

Adjust for High Altitude

 ................................... 

13

 

 

Checklist for Gas and Electricity

 ....................... 

13

 

 

Installation of Temperature Controller

 ............ 

14

 

Mounting the Controller

 .................................. 

15

 

 

Final Checklist

................................................... 

16

 

Installer Qualifications

 

DO NOT

 

• 

Do not install the V53De indoors.

 

• 

Do not install the appliance in an area where water 
leakage of the unit or connections will result in 
damage to the area adjacent to the appliance or to 
lower floors of the structure.  When such locations 
cannot be avoided, it is recommended that a 
suitable drain pan, adequately drained, be installed 
under the appliance.  The pan must not restrict 
combustion air flow.

 

• 

Do not obstruct the flow of combustion and 
ventilation air.  Combustion air shall not be 
supplied from occupied spaces.

 

• 

Do not use this appliance in an application such as 
a pool or spa heater that uses chemically treated 
water .  (This appliance is suitable for filling large or 
whirlpool spa tubs with potable water.)

 

• 

Do not use substitute parts that are not authorized 
for this appliance.

 

MUST DO

 

• 

The installation must conform with local codes or, 
in the absence of local codes, with the 

National 

Fuel Gas Code, ANSI Z223.1/NFPA 54

, or the 

Natural Gas and Propane Installation Code, CSA 
B149.1

.  If installed in a manufactured home, the 

installation must conform with the 

Manufactured 

Home Construction and Safety Standard, Title 24 
CFR, Part 3280

 and/or 

CAN/SCA Z240 MH Series, 

Mobile Homes

.  

 

• 

The appliance, when installed, must be electrically 
grounded in accordance with local codes or, in the 
absence of local codes, with the 

National Electrical 

Code, ANSI/NFPA 70

, or the 

Canadian Electrical 

Code, CSA C22.1.

 

• 

The appliance and its appliance main gas valve 
must be disconnected from the gas supply piping 
system during any pressure testing of that system 
at test pressures in excess of 1/2 psi (3.5 kPa) 
(13.84 in W.C.).

 

• 

The appliance must be isolated from the gas supply 
piping system by closing its individual manual 
shutoff valve during any pressure testing of the gas 
supply piping system at test pressures equal to or 
less than 1/2 psi (3.5 kPa) (13.84 in W.C.).

 

• 

You must follow the installation instructions for 
adequate combustion air intake and exhaust.

 

INFORMATION

 

• 

If a water heater is installed in a closed water 
supply system, such as one having a backflow 
preventer in the cold water supply line, means 
shall be provided to control thermal expansion. 
Contact the water supplier or local plumbing 
inspector on how to control thermal expansion.

 

Type of installation

 

• 

For installation in residential applications.  

 

• 

Certified for installation in manufactured (mobile) 
homes.

 

Содержание RU180iN

Страница 1: ...manual must be left for the consumer The consumer must read and refer to this manual for proper operation and to maintain the water heater If the information in these instructions is not followed exa...

Страница 2: ...Electricity 13 Installation of Temperature Controller 14 Mounting the Controller 15 Final Checklist 16 Technical Data 17 Specifications 17 Dimensions 18 Pressure Drop and Water Flow Curves 19 Ladder...

Страница 3: ...diately below the water heater or by turning off the water supply to the building WARNING AVERTISSEMENT Use only your hand to push in or turn the gas control knob Never use tools If the knob will not...

Страница 4: ...d water This appliance is suitable for filling large or whirlpool spa tubs with potable water Do not use substitute parts that are not authorized for this appliance MUST DO The installation must confo...

Страница 5: ...onment water quality and need for freeze protection Requirements for the gas line water lines electrical connection and Should overheating occur or the gas supply fail to shut off turn off the manual...

Страница 6: ...30 cm for appliances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening K Clearance to a mechanical...

Страница 7: ...that are found in aerosol sprays detergents bleaches cleaning solvents oil based paints varnishes and refrigerants The air in beauty shops dry cleaning stores photo processing labs and storage areas f...

Страница 8: ...Mobile Homes Leave the entire manual taped to the temperature controller if installed or give the entire manual directly to the consumer Mount to Wall 1 Identify the installation location and confirm...

Страница 9: ...Z21 22 and or the standard Temperature Pressure Temperature and Pressure Relief Valves and Vacuum Relief Valves CAN1 4 4 The relief valve must be rated up to 150 psi and to at least the maximum BTU h...

Страница 10: ...ump Solenoid Valve Boiler Drain Valve KEY This is not an engineered drawing It is intended only as a guide and not as a replacement for professionally engineered project drawings This drawing is not i...

Страница 11: ...rmance Installation of Gas Supply MUST DO A manual gas control valve must be placed in the gas supply line to the water heater A union can be used on the connection above the shut off valve for the fu...

Страница 12: ...the 3 4 inch pipe size is capable of supplying 188 FT3 HR of natural gas Gas Input of all gas products BTU HR Heating Value of Gas BTU FT 3 Cubic Feet per Hour CFH Any compound used on the threaded jo...

Страница 13: ...klist for Gas and Electricity A manual gas control valve is placed in the gas line to the water heater Check the gas lines and connections for leaks Confirm that the gas inlet pressure is within limit...

Страница 14: ...Controllers Maximum Cable Length for each Controller to Water Heater 1 328 ft 100 m 2 164 ft 50 m 3 or 4 65 ft 20 m Turn the power off Do not attempt to connect the temperature controllers with the p...

Страница 15: ...using the holes drilled in step 2 7 Disconnect power from the water heater 8 Remove the screw on the Quick Cable Connector Fig 1 9 Rotate the Quick Cable Connector Fig 2 10 Route the wires through th...

Страница 16: ...t pressure is within limits Confirm that the water heater is rated for the gas type supplied Confirm that the electricity is supplied from a 120 VAC 60 Hz power source is in a properly grounded circui...

Страница 17: ...more information 140 F 60 C Minimum Temperature Setting 115 F 46 C Weight 29 7 lb 13 5 kg Noise level 54 dB Electrical Consumption Normal 50W Standby 2 W Anti frost Protection 64W Max Current 1 2A Fu...

Страница 18: ...ot Water Outlet from wall 3 4 87 F Hot Water Outlet from center 4 1 105 G Cold Water Inlet from wall 2 7 68 H Cold Water Inlet from center 0 4 10 I Gas Connection from wall 3 0 77 J Gas Connection fro...

Страница 19: ...V53De Manual 19 Pressure Drop Curve Water Flow Curve 0 0 1 0 2 0 3 0 4 0 5 0 6 0 0 25 50 75 100 125 150 delta T Temperature Rise F Pressure Loss ft head Water Flow gpm Water Flow gpm Pressure Loss psi...

Страница 20: ...20 V53De Manual Ladder Diagram...

Страница 21: ...product s you registered and or you account with us Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Leave...

Страница 22: ...eau m me partiellement Faites inspecter l appareil par un technicien qualifi et remplacez toute partie du syst me de contr le et toute commande qui ont t plong s dans l eau TO TURN OFF GAS TO APPLIANC...

Страница 23: ...art of the control system and any gas control which has been under water N utilisez pas cet appareil s il a t plong dans l eau m me partiellement Faites inspecter l appareil par un technicien qualifi...

Страница 24: ...water sources are able to provide water at this temperature setting until it is changed again at this or another temperature controller DANGER Hot water can be dangerous especially for infants or chi...

Страница 25: ...cked by pressing the Priority button and the up button together for 5 seconds A beep will sound confirming that the controller is locked The display will alternately show LOC the temperature setting a...

Страница 26: ...Push Button 3 PB3 White MENU button cycles through available menus 1 2 3 4 5 and 6 see table below 4 Push Button 4 PB4 White VALUE button cycles through available menu values see table below 5 Push B...

Страница 27: ...and or regulator is sized properly Ensure gas type and pressure is correct Bleed all air from gas lines Ensure condensation collar was installed properly Verify dip switches and programming parameter...

Страница 28: ...istance of motor winding 70 PC Board Replace the PC Board 71 Solenoid Valve Circuit Replace the PC Board 72 Flame Sensing Device Verify flame rod is touching flame when unit fires Check all wiring to...

Страница 29: ...he water must be potable free of corrosive chemicals sand dirt or other contaminates It is up to the installer to ensure the water does not contain corrosive chemicals or elements that can affect or d...

Страница 30: ...te trap is not affected by the auto drain down solenoid valves and will have to be manually drained Winterizing These recommendations are intended to suggest practices which are effective for winteriz...

Страница 31: ...lons of undiluted virgin food grade white vinegar into pail 6 Place the drain hose H3 and the hose H2 to the pump inlet into the cleaning solution 7 Open both service valves V1 and V2 on the hot water...

Страница 32: ...tap and confirm that water flows and then close 6 Turn on the power 7 After confirming that the temperature controller is off turn on the gas supply 8 Turn on the temperature controller Running a low...

Страница 33: ...s used It can be activated by a push button motion sensor or voice activation but not by a temperature sensor A timer added to a standard recirculating pump is not considered as on demand 2 The air ha...

Страница 34: ...n product installed in a closed loop application commonly associated with space heating only applications The integrated controller on indoor models has a 1 year warranty on parts There is no warranty...

Страница 35: ...NOTES...

Страница 36: ...U340 1338 02 100000561 03 7 2019...

Отзывы: