• © 2009 Rinnai America Corporation
32
PARA
Description
Range / Explanation
Factory
Setting
User
Access
12
Min. temp
limit
50
°F to max
temp
Minimum boiler temperature limit in heating
mode NOTE: This overrides Boiler Para 27
68
°F
No
Unmixed (HC) Circuit Parameters
(continued)
13
Max. temp
limit
Min. temp
to 176
°F
Maximum boiler temperature limit in
heating mode.
176
°F
No
NOTE: If parameter 1 in the boiler is lower, it will override this setting; NOTE: This value will go to 203
°F but the
boiler will never eclipse 176
°F; NOTE: 176°F=Default at shipment, 158°F=Default at System Reset
14
NA
-9 to 36
°F
Not for use with the RS100. Do not adjust
0
°F
No
23
NA
1 to 100
Do not adjust (temp)
8
No
24
NA
5
–240
Do not adjust (minutes)
15
No
25
Daytime
room temp
base value
41 to 86
°F
Daytime base value for room temp (Note:
This setting is not needed as there is a
button on the front for it)
70
°F
Yes
26
Nighttime
room temp
base value
41 to 86
°F
Nighttime base value for room temp (Note:
This setting is not needed as there is a
button on the front for it)
61
°F
Yes
27
K-Factor
(curve slope)
0.2 to 3.5
Higher number=steeper the curve.
NOTE: this can be adjusted from
the front panel button. It is not
needed if Para 3=1 and Para 4=RC.
1.50
Yes