• © 2009 Rinnai America Corporation
30
PARA
Description
Range / Explanation
Factory
Setting
User
Access
3
Controller
application
type
(Outdoor
reset or RC
mode)
OFF
Outdoor reset mode: The RS100 doesn’t use the
room temp for operation. Boiler supply temp is
displayed (pressing the dial displays room temp).
1
Yes
1
Room Control/RC Mode: Controller fully enabled
(recommended)
3
Outdoor reset mode: The RS100
doesn’t use the
room temp for operation but it will be displayed
If
OFF or 3 is selected the boiler’s pump continuously operates. The boiler will fire based on the outside sensor.
NOTE: 1=Default at shipment, 3=Default at System Reset
4
Controller
effect type
(Parameter 3
must be set
to 1)
OFF
The boiler’s pump continuously operates. The
boiler will fire based on the outside sensor. Boiler
supply temp is displayed.
RC
Yes
10-
500%
Do not use these settings
RC
The boiler will operate based only on the
RS100’s area temperature sensor
NOTE: RC=Default at shipment, OFF=Default at System Reset
Unmixed (HC) Circuit Parameters
(continued)
5
N/A
OFF
/ON
This should not be altered
OFF
Yes