Rinnai
20
Installation Manual
FLUE INSTALLATION
FLUE TERMINAL LOCATION
The flue terminal should be positioned away from flammable materials.
The RHFE-752ETR flue terminal is ‘Fan Assisted’ with a maximum input
of 32 MJ/h
Ensure that the location of the flue terminal can comply with the
requirements of AS/NZS 5601 - Fig. 6.2 which is reproduced below.
AS/NZS 5601 was current at the time of printing but may have been superseded. It is the
installer’s responsibility to ensure that requirements of the current version of AS/NZS 5601
are met.
When installing the condensate trap kit (ESCONDK) the included condensate tray MUST BE
fitted. Consult the Rinnai “Power Flued Flamefire Space Heater Co-axial Flue System
Installation Manual” supplied with flue kits ASPDFK or ASPKIT03 for installation
instructions.
The flue system must be fully assembled and secured in place before the heater is installed
into the enclosure.
WARNING
Flue terminal
Fan assisted flue appliance only
Gas meter
Electricity meter or fuse box
Mechanical air inlet
Natural draft Fan assisted
•
Appliances
up to 50 MJ/h input
300
200
•
Appliances
over 50 MJ/h input
500
300
b
From the ground, above a balcony or other surface *
300
300
c
Front a return wall or external corner *
500
300
d
From a gas
meter
(M) (see 5.11.5.9 for vent terminal location of
regulator
)
(see Table 6.6 for New Zealand requirements)
1000
1000
e
From an electricity
meter
or fuse box (P) †
500
500
f
From a drain pipe or soil pipe
150
75
g
Horizontally from any building structure* = or obstruction facing a terminal
500
500
h
From any other
flue terminal
, cowl, or combustion air intake †
500
300
•
Appliances
up to 150 MJ/h input *
500
300
•
Appliances
over 150 MJ/h input up to 200 MJ/h input *
1500
300
•
Appliances
over 200 MJ/h input up to 250 MJ/h input *
1500
500
•
Appliances
over 250 MJ/h input *
1500
1500
• All fan-assisted
flue appliances
, in the direction of discharge
-
1500
k
From a mechanical air inlet, including a spa blower
1500
1000
• Space heaters up to 50 MJ/hr input
150
150
• Other
appliances
up to 50 MJ/hr input
500
500
•
Appliances
over 50 MJ/h input and up to 150 MJ/h input
1000
1000
•
Appliances
over 150 MJ/h input
1500
1500
1
Where dimensions
c, j
or
k
cannot be achieved an equivalent horizontal distance
measured diagonally from the nearest discharge point of the terminal to the opening
may be deemed by the Technical Regulator to comply.
2
See Clause 6.9.4 for restrictions on a
flue terminal
under a covered area.
3
See Figure J3 for clearances required from a
flue terminal
to an LP Gas
cylinder.
A
flue terminal
is considered to be a source of ignition.
4
Ref.
Item
a
Min. clearances (mm)
Below eaves, balconies and other projections:
j
Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a building
with the exception of sub-floor ventilation:
Vertically below an openable window, non-mechanical air inlet, or any other opening into a building with the
exception of sub-floor ventilation:
NOTES:
† - Prohibited area below electricity meter or fuse box extends to ground level.
FIGURE 6.2 (in-part) MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS, FAN-ASSISTED FLUE
TERMINALS, ROOM-SEALED APPLIANCE TERMINALS AND OPENINGS OF OUTDOOR APPLIANCES
* - unless
appliance
is
certified
for closer installation
For
appliance s
not addressed above acceptance should be obtained from the Technical Regulator.
n
NOTE
IMPORTANT