Rinnai Tankless Water Heater Installation and Operation Manual

 

35    

Important: 

Combustion air must be free of corrosive chemicals. Do not provide combustion air from corrosive 

environments. Appliance failure due to corrosive air is not covered by warranty.

 

For applications containing corrosive indoor air, this appliance must be installed as direct vent. DO NOT use room air in 
applications where combustion air contains acid forming chemicals such as sulfur, fluorine and chlorine. These 
chemicals have been found to cause rapid damage and decay and can become toxic when used as combustion air in 
gas appliances. Such chemicals can be found in, but not limited to bleach, ammonia, cat litter, aerosol sprays, cleaning 
solvents, varnish, paint and air fresheners. Do not store these products or similar products in the vicinity of this water 
heater.

 

Unconfined Space

 

An unconfined space is defined in 

National Fuel Gas Code, ANSI Z223.1/NFPA 54

 as 

a space whose volume is not less 

than 50 cubic feet per 1000 Btu/hr (4.8 m3 per kW per hour) of the aggregate input rating of all appliances installed in 
that space. Rooms communicating directly with the space in which the appliances are installed, through openings not 
furnished with doors, are considered a part of the unconfined space.

” 

If the 

unconfined space

” 

containing the 

appliance(s) is in a building with tight construction, additional outside air may be required for proper operation. 
Outside air openings should be sized the same as for a confined space.

 

Confined Space 

 

A confined space is defined in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54 

as "a space whose volume is less than 

50 cubic feet per 1000 Btu/hr (4.8 m3 per kW per hour) of the aggregate input rating of all appliances installed in that 
space." Examples include a small room, closet, alcove, utility room, etc. A confined space must have two combustion 
air openings. Size the combustion air openings based on the BTU input for all gas utilization equipment in the space 
and the method by which combustion air is supplied. 

 

Using Indoor Air For Combustion: 

When using air from other room(s) in the building, the total volume of the room(s) 

must be of adequate volume (Greater than 50 cubic feet per 1000 Btu/hr). Combustion air openings between joining 
rooms must have at least 1 square inch of free area for each 1000 Btu/h, but not less than 100 square inches each.

 

Using Outdoor Air For Combustion

 

Outdoor air can be provided to a confined space through two permanent openings, one commencing within 12 in. 

 

(0.30 m) of the top and one commencing within 12 in. (0.30 m) of the bottom, of the confined space. The openings 
shall communicate to the outside by one of two ways.

 

When communicating directly with the outdoors through horizontal ducts, each opening shall have a minimum free 
area of 1 in

2

/2000 Btu/hr (1100 mm

2

/kW) of total input rating of all appliances in the confined space. 

 

Note: If ducts are used, the cross sectional area of the duct must be greater than or equal to the required free area of 
the openings to which they are connected.

 

This water heater requires adequate combustion air for ventilation and dilution of flue gases. Failure to provide 

 

adequate combustion air can result in unit failure, fire, explosion, serious bodily injury or death. Use the following 
methods to ensure adequate combustion air is available for correct and safe operation of this water heater.

 

     

WARNING

 

Combustion Air

 

Non

-

Direct Vent   

(Room Air) 

 

2

 

Содержание REU-N2024FF-US

Страница 1: ...allumer d appareil Ne touchez aucun interrupteur ne pas vous servir des t l phones se trouvant dans le b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions...

Страница 2: ...3 8 Pressure Relieve Valve 43 3 9 Condensate 45 3 10 Connect the Gas Supply 47 3 11 Connect the Power Supply 50 3 12 Parameter Settings 51 3 13 External Pump with Circ Logic 52 3 14 Service Indicator...

Страница 3: ...manual before installing the water heater The water heater must be installed according to the exact instructions in this manual Proper installation is the responsibility of the installer When install...

Страница 4: ...n personal injury or death Indicates a potentially hazardous situation which if not avoided could result in minor or moderate injury It may also be used to alert against unsafe practices Safety alert...

Страница 5: ...et d arr t de l admission de gaz Only trained and qualified professionals are permitted to adjust parameter settings Do not use an extension cord or adapter plug with this appliance Any alteration to...

Страница 6: ...eens x2 and vent screen screws x2 for internal indoor water heaters only The vent screen prevents debris and other objects from entering the terminal One vent screen is for the intake the other is for...

Страница 7: ...res and communicates with the service provider portal The Control R Wi Fi Module and MC 195T US controller are not compatible accessories and must not be installed together Recirculation Pump A pump s...

Страница 8: ...PM 38 L min 9 GPM 34 L min 7 GPM 26 L min 11 GPM 42 L min 10 GPM 38 L min 9 GPM 34 L min 7 GPM 26 L min Weight 64 lb 29 kg 64 lb 29 kg 62 lb 28 kg 62 lb 28 kg 64 lb 29 kg 64 lb 29 kg 62 lb 28 kg 62 lb...

Страница 9: ...door Models RU199i RU180i RU160i and RU130i Front Panel View Side Panel View External Outdoor Models RU199e RU180e RU160e and RU130e Front Panel View Side Panel View 2 6 Dimensions Vent Connection 2 i...

Страница 10: ...0 Rinnai Tankless Water Heater Installation and Operation Manual Connections for Internal and External Water Heaters Pressure Relief Valve PRV M33 THREAD Bottom View of Water Heater Measurements in mm...

Страница 11: ...ressures less than or equal to 1 2 psi 3 5 kPa 13 84 in W C the appliance must be isolated from the gas supply piping by closing its individual manual shutoff valve You must follow the installation in...

Страница 12: ...information is intended to serve as general guidelines only and is not a complete list of water quality guidelines 3 2 Choose an Installation Location Air surrounding the water heater venting and vent...

Страница 13: ...ve Loss of freeze protection may result in water damage from a burst heat exchanger or water lines The water heater may be drained manually However it is highly recommended to install the optional Dra...

Страница 14: ...ounds in the air The water heater location complies with the required clearances The planned combustion air and exhaust termination locations meet the required clearances The water supply does not con...

Страница 15: ...ws on far left side and 2 screws on far right side Use the appropriate screws for the wall construction to secure the mounting bracket to the wall between two studs Securely screw the top and bottom b...

Страница 16: ...ake sure the water heater is straight Proper operation requires the water heater to be level Make sure the securing method is sufficient to support the weight of the water heater Refer to the water he...

Страница 17: ...ems vent connections must be firmly pressed together so that the connections form an air tight seal Follow the venting manufacturer s instructions Refer to the PVC CPVC manufacturer for appropriate fi...

Страница 18: ...locations near a dryer vent Avoid termination locations near commercial cooking exhaust Avoid termination locations near any air inlets You must install a vent termination at least 12 in above the gr...

Страница 19: ...er and a separate exhaust header that vents directly through separate penetrations to the outside Combustion Air Exhaust Exhaust Room Air For Combustion Twin Pipe Combustion air and exhaust vent direc...

Страница 20: ...29 www duravent com Royal 800 232 5690 www royalbuildingproducts com Ecco Manufacturing 877 955 4805 www eccomfg com DiversiTech 800 995 2222 www diversitech com Direct Vent Approved Vent Manufacturer...

Страница 21: ...x 40 in 20 ICRT2439 2 in x 4 in Concentric Roof Termination 20 2PPS VKL VK TCL 2 in x 4 in Vertical Termination Cap Kit Concentric 20 2PPS HKL 2 in x 4 in Horizontal Termination Kit Concentric 20 190...

Страница 22: ...above roof 5 196006 197009 FGV Concentric Vent Kit 3 in x 20 in 20 196106 197107 FGV Concentric Vent Kit 3 in x 32 in 20 196116 197117 FGV Concentric Vent Kit 3 in x 44 in 20 52CVKGVS6503 PVC 52CVKGV...

Страница 23: ...al Termination 16 3PPS VKL VK TCL 3 in x 5 in Vertical Termination Cap Kit Concentric 20 3PPS HKL 3 in x 5 in Horizontal Termina tion Kit Concentric 20 190388 3 in x 5 in Concentric Horizontal Termina...

Страница 24: ...in Pipe Termination 10 2PPS HSTL 2 in Single Horizontal Termination 6 2PPS TBL 2 in Black UV Resistant Tee 5 196984 FGV PVC Low Profile Termination Kit 5 081216 FGV PVC Wall Termination Kit 16 52SWVKG...

Страница 25: ...Horizontal Termination 5 3PPS TBL 3 in Black UV Resistant Tee 6 196985 FGV PVC Low Profile Termination Kit 5 081219 FGV PVC Wall Termination Kit 16 52SWVKGVS6503 PVC Side Wall Vent Kits 5 52WTVKGVS65...

Страница 26: ...64 CPVC Schedule 40 ANSI ASTM F493 PVC Vent Screens Termination Vent Screens Polyethylene 2 in Vent Screens included in carton box IPEX Part Number 196050 3 in Vent Screens IPEX Part Number 196051 Exh...

Страница 27: ...non mechanical air supply inlet to building or the combustion air inlet to any other appliance 36 in 91 cm 12 in 30 cm K Clearance to a mechanical air supply inlet 6 ft 1 83 m 3 ft 91 cm above if with...

Страница 28: ...ls at different levels Note 24 in 0 61 m to wall or parapet Combustion air and exhaust vent directly through a single concentric connection Hot exhaust exits through the interior tube while combustion...

Страница 29: ...Vent Maximum Equivalent Length Vent Sizes 2 in X 4 in 3 in X 5 in Vent Lengths 65 ft 20 m 150 ft 46 m 45 elbow is equivalent to 3 ft 1 m 90 elbow is equivalent to 6 ft 2 m Concentric Pipe Installatio...

Страница 30: ...case scenario of 3 X 90 elbows or 18 equivalent ft Twin Pipe Vertical Termination of Multiple Water Heaters Combustion air termination not permitted in shaded area Horizontal Vent and Combustion Air P...

Страница 31: ...he use of a pipe reducer installers can use a 3 in 76 mm pipe for the combustion air and exhaust Remove and discard the screw from the combustion air vent connection Remove and discard the combustion...

Страница 32: ...tion 2 in or 3 in PVC Low Profile Termination Configuration This configuration requires the use of a Concentric Vent Termination Exhaust and combustion air MUST NOT be brought together into a single P...

Страница 33: ...tance of 15 ft 4 m J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 36 in 91 cm 4 ft 1 2 m below or to side of opening 1 ft 300 mm above op...

Страница 34: ...ipated snow level 2 in 0 91 m to ventilated or unventilated soffit or eve vent or to a deck or porch Termination Clearances for External Outdoor Water Heaters Exhaust Termination Clearances for Intern...

Страница 35: ...me is less than 50 cubic feet per 1000 Btu hr 4 8 m3 per kW per hour of the aggregate input rating of all appliances installed in that space Examples include a small room closet alcove utility room et...

Страница 36: ...e regulations therein Checklist for Combustion Air and Venting Requirements Location To maintain proper circulation of combustion air two permanent openings one upper one lower must be positioned in c...

Страница 37: ...ure with the supplied screw Use the room air screen for environments where room air is dusty Note 2 in vent screen supplied with water heater Room air screen is available as an accessory Glue elbow to...

Страница 38: ...Non Direct Vent Room Air Example Vent Applications Non Direct Vent Room Air Maximum Vent Length Non Direct Vent Room Air 2 Room Air Maximum Equivalent Length Table Vent Sizes 2 in 51 mm 3 in 76 mm 2 i...

Страница 39: ...ets on the back side of the water heater Installation Enclosure with Louvered Door for Manufactured Home Applications Use the following chart to identify the minimum required size of the opening in th...

Страница 40: ...ent Diameter Max System Btu hr 3 in 4 in 6 in RU199i REU N3237FF US RU180i REU N2934FF US 2 398 000 360 000 65 ft 20 m 150 ft 46 m 150 ft 46 m RU160i REU N2530FF US RU130i REU N2024FF US 2 320 000 260...

Страница 41: ...T Water connections to the water heater should follow all state and local plumbing codes If this is a standard installation refer to the Piping Diagram for Basic Installation below 1 Plumb the cold wa...

Страница 42: ...Hot Outlet side of the water heater 2 Hand tighten the Swivel Nut of the Hot Isolation Valve Red to the Hot Outlet side of the water heater 3 Rotate the Drain Valve to an accessible position With a wr...

Страница 43: ...Fahrenheit The pressure relief valve is assembled to the pressure relief valve adapter as illustrated on the next page DO NOT place any other valve or shut off device between the pressure relief valv...

Страница 44: ...the steps below 1 On the bottom of the tankless water heater hand tighten the Pressure Relief Valve Assembly and Gasket to the Pressure Relief Valve Union Fitting 2 Rotate the Pressure Relief Valve A...

Страница 45: ...on and an interior wall If a floor drain is not available or the drain is above the level of the condensate drain a condensate pump should be installed A condensate neutralizer kit is available from R...

Страница 46: ...Condensate Pump Safety Switch Installation NC NO COM Tankless Water Heater Test Operation 1 Test the operation of the shut off switch by unplugging the condensate pump and filling the condensate reser...

Страница 47: ...solutions including soap and water may cause corrosion or stress cracking the piping shall be rinsed with water after testing unless it has been determined that the leak test solution is non corrosive...

Страница 48: ...xample The appropriate table from the applicable code must be used Schedule 40 Metallic Pipe Inlet Pressure Less than 2 psi Specific Gravity 0 60 Gas Pipe Sizing Reference Tables Information in table...

Страница 49: ...24 147 308 580 1 190 90 27 138 289 544 1 120 100 30 131 273 514 1 060 Information in table obtained from NFPA 54 ANSI Z223 1 2015 Information in table obtained from NFPA 54 ANSI Z223 1 2015 Intended...

Страница 50: ...ly Connection Checklist When connecting the power supply follow these guidelines Do not rely on the gas or water piping to ground the water heater Ground locations are provided inside the water heater...

Страница 51: ...109 m 03 Service Soon1 Disabled 0 5 Year 1 Year 2 Years 04 Recirculation Settings No Recirculation Recirculation Dedicated 05 Recirculation Mode2 Economy Comfort 06 Control Switch BMS3 Air Handler AH...

Страница 52: ...gs the external pump cable is not included with the tankless water heater and must be purchased separately Circ Logic operates in either Economy or Comfort mode based on the parameter settings of the...

Страница 53: ...es to the tankless water heater are not interchanged Does the water supply to the heater have adequate pressure Is it free of chemicals Did you verify it does not exceed total hardness that will damag...

Страница 54: ...ndensate drain pipe is open to atmosphere GAS SUPPLY YES NO Did you verify the gas system is appropriately sized Did you verify the water heater is rated for the gas type supplied Have you performed a...

Страница 55: ...ch as chlorine or bleach that produce fumes These fumes can damage components and reduce the life of your appliance Damage and repair due to scale in the heat exchanger is not covered by warranty Alwa...

Страница 56: ...the beeps repeat the above steps 1 To lock the internal controller press and hold down the Priority button 2 While holding down the Priority button press the Up button until a beep is heard approxima...

Страница 57: ...when you are not getting hot water or if the water alternates between hot and cold it is due to the water flow being below or close to the minimum flow rate Increasing the flow rate should resolve the...

Страница 58: ...s to scroll to the desired information described in the Performance Data Table 4 To exit performance data repeat step 2 above 5 When complete the set temperature appears in the display 1 2 DATA UNIT 0...

Страница 59: ...ter Not Turning On Check that the gas is turned on at the water heater meter or cylinder If the system is propane make sure that gas is in the tank Ensure gas type and inlet gas pressure are correct B...

Страница 60: ...required to fire unit Measure the resistance of the water flow control sensor Clean inlet water supply filter On new installations ensure hot and cold water lines are not reversed 19 Electrical Groun...

Страница 61: ...professional must verify proper operation after servicing The following maintenance items are required for the proper operation of your water heater 5 Maintain the Water Heater 5 1 Maintenance VENT S...

Страница 62: ...and will have to be manually opened WINTERIZATION The following recommendations are intended to suggest practices that are effective for winterizing the water heater They should be used as a guide onl...

Страница 63: ...ecuring the front panel Remove the front panel and locate the filter at the upper right hand corner of the water heater Remove the air filter by pulling out the FILTER Pull to Clean tab 5 2 Cleaning a...

Страница 64: ...Allow water to flow through the water heater for five minutes d Close shutoff valve V4 When unit has finished draining remove the in line filter at the cold water inlet and clean out any residue Plac...

Страница 65: ...ater heater and the piping for leaks HOT COLD ON To avoid burns wait until the equipment cools down before draining the water The water in the appliance will remain hot after it is turned off WARNING...

Страница 66: ...66 Rinnai Tankless Water Heater Installation and Operation Manual 6 Appendices 6 1 Wiring Diagram PC BOARD...

Страница 67: ...Rinnai Tankless Water Heater Installation and Operation Manual 67 6 2 Ladder Diagram...

Страница 68: ...ase contact Rinnai Delta T Temperature Rise F Water Flow GPM Dashed lines represent flow rate after parameter adjustment RU130 RU160 RU180 RU199 6 3 Pressure Drop and Water Flow Curves Pressure Loss f...

Страница 69: ...Location The temperature controller should be out of reach of small children Avoid locations where the temperature controller may become hot near an oven or radiant heater Avoid locations in direct su...

Страница 70: ...er to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors A In the event that the side wall horizontally vented gas fueled equipment is...

Страница 71: ...Rinnai Tankless Water Heater Installation and Operation Manual 71 COMBINATION SPACE HEATING POTABLE WATER SYSTEM For Use In Commonwealth of Massachusetts Massachusetts State Regulations Continued...

Страница 72: ...curs first if the Rinnai Tankless Water Heater temperature settings exceed 160 F 71 C The integrated controller has a 1 year warranty on parts What Will Rinnai Do Rinnai will repair or replace the cov...

Страница 73: ...horized to make any other warranties on behalf of Rinnai America Corporation Except as expressly provided herein there are no other warranties expressed or implied including but not limited to warrant...

Страница 74: ...74 Rinnai Tankless Water Heater Installation and Operation Manual 7 Notes...

Страница 75: ...Rinnai Tankless Water Heater Installation and Operation Manual 75 Notes...

Страница 76: ...76 Rinnai Tankless Water Heater Installation and Operation Manual 100000467 05 8 2019...

Отзывы: