Installation & Servicing Instructions Rinnai Q-Series
63
- remove and replace the gasket;
Refitting of the components is done in reverse order.
Condensate trap and condensate tray (figure 36-38) (2 and 4 year maintenance)
Step 1: Condensate trap
- first remove the condensation cup (7);
Check this for impurities. If there is not a lot of impurities it is not necessary to
clean the condensate tray (Go to Step 3). If there is a lot of impurities in the cup
it is necessary to remove and clean the condensate tray according Step 2;
- remove the inner trap pipe (8) which remains in the condensate tray;
- check the O-rings of the cup as well as those from the pipe and replace if necessary;
- clean both parts by flushing it with clean water;
- grease the O-rings again with acid free O-ring grease to make fitting easier;
- if there is a leak at the condensation cup (7) or tray (9) the complete condensate
trap unit (10) has to be replaced by S4451610;
Step 2: Condensate tray
- remove the plug from the flue gas sensor if present;
- turn the two short clamping rods (11 and 12) ¼ turn and remove them by pulling
them forward;
Note the correct turning direction (red indicator, fig. 38)
;
- lift the exhaust pipe (13) out of the condensate tray (14);
- press the condensate tray (14) carefully downwards and remove it by pulling it forward;
- replace the gasket between condensate tray and heat exchanger by a new one;
- clean the condensate tray with water and a hard brush;
- check the condensate tray on leaks.
Step 3:
Refitting is done in reverse order.
Note that all gaskets seals completely.
Make sure that during refitting the clamping rods they are put in the right
position. They should be turned vertical.
If the boiler should activated with clamping rods in the wrong position it will
cause serious property damage, personal injury or loss of life.
Put the boiler into operation and check the O
2
(see page 58).
If replacement by new gaskets and burner mentioned in this chapter is not done
within the service interval subscribed by Rinnai the boiler can be damaged and
will cause serious property damage, personal injury or loss of life.
Use only original spare parts supplied by Rinnai. If other parts will be used
the boiler can be damaged and will cause serious property damage, personal
injury or loss of life. Use of non-Rinnai parts will result in the void of warranty.
!
DANGER
!
DANGER
!
WARNING
Clamping rods
figure 38
Condensate tray
figure 37
Siphon
figure 36
11
12
13
14
7
8
9
10
Содержание Q130SN
Страница 18: ...Installation Servicing Instructions Rinnai Q Series 18 Boiler basic piping fig 6 ...
Страница 44: ...Installation Servicing Instructions Rinnai Q Series 44 electrical ladder diagram figure 22a ...
Страница 99: ...Installation Servicing Instructions Rinnai Q Series 99 ...
Страница 119: ...Installation Servicing Instructions Rinnai Q Series 119 ...
Страница 120: ......
Страница 138: ...Installation Servicing Instructions Rinnai Q Series 138 Tuyeauterie de base de chaudière fig 6 ...
Страница 165: ...Installation Servicing Instructions Rinnai Q Series 165 Schéma électrique en échelle figure 22a ...