Installation & Servicing Instructions Rinnai Q-Series
51
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
STEP 7
STEP 8
NOTICE
i
NOTICE
i
11
Adjustments
When the boiler is installed it is ready for use. All adjustments of the boiler control
are already pre-programmed for a heating system with radiators/convectors with a
supply temperature of 185°F. The adjustments are described in the Parameter chapter
on page 44.
In certain cases parameters have to be altered in case of :
- Lower supply temperature
- High altitude/long vent length
Read through the Parameter chapter to adjust the boiler to its installation.
Contact Rinnai in case of doubt.
Only qualified personel who are trained for servicing these boilers are permitted
to make alterations in the controller to calibrate the boiler to the installation.
11.1 Altering adjustments
Press the Mode-button for 5 seconds.
The display shows COdE followed by an arbitrary number;
Press by means of the + or the - button until the code C123 is shown;
Press the STORE-button to confirm the code (code blinks1 x).
Now you have acces to the installer level. There are 4 chapters:
•
Parameters
•
Information chapter (no adjustments possible)
•
Service chapter
•
Error-chapter (no adjustments possible)
The content of the chapters is described on the following pages.
Press briefly the MODE-button to select one of the 4 chapters, i.e. PARA;
Press once or more briefly on the STEP-button to select a Parameter
(parameter visible on the left, value on the right) ;
Alter the value, if necessary/possible, by means of the + or the - button
Press briefly on the STORE-button to confirm the alteration.
When you have to change more values, repeat from step 5.
Press once or more on the MODE-button until StBY or Good is shown:
After a few seconds the text StBY will be replaced by the technical read-out
or Good-state (Depending from the position the acces code is entered)
When you want to return from an arbitrary position to the original read out
press once or more on the MODE-button until StBY is shown.
If no single button is used within 20 minutes the display will return automatically to its
original read-out (Good state or technical read out)
Содержание Q130SN
Страница 18: ...Installation Servicing Instructions Rinnai Q Series 18 Boiler basic piping fig 6 ...
Страница 44: ...Installation Servicing Instructions Rinnai Q Series 44 electrical ladder diagram figure 22a ...
Страница 99: ...Installation Servicing Instructions Rinnai Q Series 99 ...
Страница 119: ...Installation Servicing Instructions Rinnai Q Series 119 ...
Страница 120: ......
Страница 138: ...Installation Servicing Instructions Rinnai Q Series 138 Tuyeauterie de base de chaudière fig 6 ...
Страница 165: ...Installation Servicing Instructions Rinnai Q Series 165 Schéma électrique en échelle figure 22a ...