Installation & Servicing Instructions Rinnai Q Premier
58
Service Mode
SERV
VALUE
DESCRIPTION
RANGE
1
OFF
boiler in operation with burner function on
OFF - max.
2
OFF
fan adjustable and burner off
OFF - max.
3
OFF
pump adjustable with burner on
OFF - max.
4
OFF
showroom position ON = active and OFF = non active
ON - OFF
.
.
.
.
Error Mode
ERRO
VALUE
DESCRIPTION
Err.L - Err.5
Last saved error until 5 last previous errors
1
error code
2
operation status boiler
3
°F
supply water temperature T1
4
°F
return water temperature T2
5
kW
load (.. x3415 = .. BTU/hr)
6
%
pump capacity
* Most of the data in this table can be requested by the RS100. Most of
the adjustments which are stated in this table are unnecessary when in
combination with the Rinnai RS100 thermostat and will be taken care of
by the RS100 itself and do not have to be adjusted. For further information
regarding to the RS100 thermostat refer to the Rinnai RS100 installation
manual.
Outdoor reset
Heat curve day
Heat curve night
230
212
194
176
158
140
122
104
86
68
50
-4.0
-0.4
3.2
6.8
10.4
14.0
17.6
21.2
24.8
28.4
32.0
35.6
39.2
42.8
46.4
50.0
53.6
57.2
60.8
64.4
68.0
2.30
1.80
1.80
2.30
1.50
1.50
1.00
1.00
heating line adjustments Parameter Step 6 and 7
graph 2
outside temperature in °F
fl
ow water temperature in °F
Parameter-, Info-, Service- and Error-chapters
Table 12
NOTICE
i