Installation & Servicing Instructions Rinnai Q Premier
57
Parameter Mode
PARA
FACTORY
DESCRIPTION
RANGE
.
.
.
.
1
176°F
maximum supply temperature CH
68 - 176°F
2*
00
type of CH installation:
00 - 04
No pre-selection made.
Radiators, air heating, or convectors:
T max. supply 176°F K factor heating curve 2.3; gradient 10°F/min; gear differential 10°F
00
01 DO NOT USE
radiators with large surface areas or underfloor heating as additional heating:
T max. supply 158°F K factor heating curve 1.8; gradient 10°F/min; gear differential 10°F
02
under floor heating with radiators as additional heating:
T max. supply 140°F; K factor heating curve 1.5; gradient 8°F/min; gear differential 8°F
03
full under floor heating:
T max. supply 122°F; K factor heating curve 1.0; gradient 6°F/min; gear differential 6°F
04
3
max.
maximum power CH in kW (.. x3415 = .. BTU/hr)
min-max
4*
00
control principal with on / off thermostat:
100 % on / off thermostat
00
constant water circulation 22&23 closed contact day curve operation,
open contact night curve operation
01
5*
2.3
heating curve K-factor (see also heating curve graph)
0.2 - 3.5
6*
1.4
heating curve exponent (see also heating curve graph)
1.1 - 1.4
7*
14°F
heating curve climate zone (see also heating curve graph)
-4 - 32°F
10*
0°F
fine adjustment heating curve day temperature
-8 to 10°F
11*
0°F
fine adjustment heating curve night temperature
-8 to 10°F
14
10°F/min.
gradient speed °F/min.
0 - 28°F/min.
15*
00
Booster after night decrease*:
no
00
yes
01
23
26°F
Frost Temperature
-4 to 50°F
27
32°F
Minimum T-set CH
0 - 158°F
36
10
Type of three way valve and DHW fascility
VC 2010 / VC 8010
x0
Warming function plate heat exchanger ON
1x
Warming function plate heat exchanger OFF
2x
43
max.
Maximum power DHW in kW (.. x3415 = .. BTU/hr)
min-max
49
100%
Maximum pump capacity heating
100 %
73
0
Altitude and venting CFT. See chapter 6.7.7
0 - 100
89
00
Address
No function
-01
Bus thermostat
00
90
01
Display reading
°C and Bar
00
°F and PSI
01
.
.
.
.
Info Mode
INFO
FACTORY
DESCRIPTION
RANGE
.
.
.
.
1
°F
supply water temperature T1
4
°F
return water temperature T2
5
°F
DHW temperature T3
7
°F
outdoor temperature T4
8
°F
flue gas temperature T5 (optional sensor)
16
%
actual power in %
17
kW
actual power in kW (.. x3415 = .. BTU/hr)
18
kW
actual load in kW (.. x3415 = .. BTU/hr)
20
indication bus communication
21
GJ
consumption total in GJ (.. x 33 = .. m3)
22
GJ
consumption CH in GJ (.. x 33 = .. m3)
23
GJ
consumption DHW in GJ (.. x 33 = .. m3)
24
h
total number of burner run hours
25
h
number of burner run hours CH
26
h
number of burner run hours DHW