Listed below are common components in a
Central Heating system. Refer to the diagram
on the next page.
•
Expansion Tank
—
A properly sized
expansion tank charged to 2 PSI (14 kPa)
below the cold system pressure is required
to limit pressure changes in the heating
system. When replacing an expansion tank,
consult the expansion tank manufacturer
for sizing.
•
Air Separator
—
An air separator is needed
on the central heating supply side of the
system to remove any air that may be
present in the piping.
•
Pressure/Temperature Gauge
—
The
current pressure and temperature will
alternately be displayed on the boiler
control panel. A port for an external gauge
is present in the Primary
-
Secondary
Heating Kit accessory offered by Rinnai.
Plumb the heating supply line to the
heating supply connection on the
bottom of the boiler.
•
Pressure Relief Valve (PRV)
—
A PRV
located directly on the supply side of
the boiler is required. The PRV must be
3/4 in. with at least 30 PSI (207 kPa)
and a maximum of 45 PSI (310 kPa). A
30 PSI (207 kPa) PRV is supplied with
the boiler. A port for the central
heating PRV is present in the Primary
-
Secondary Heating Kit accessory
offered by Rinnai.
•
Oxygen Elimination
—
The boiler may
only be installed in a pressurized closed
-
loop heating system, free of air and
other impurities. If using oxygen
permeable tubing in the central heating
system, a plate heat exchanger is
necessary to isolate the tubing and
boiler.
•
Low Water Cut Off (LWCO)
—
This
boiler has a factory
-
installed pressure
sensor type LWCO. The boiler's internal
LWCO is not serviceable or adjustable.
Check your local codes to determine if
a LWCO is required and if this device
conforms to the local code. If a LWCO is
required to be installed, the probe
must be located higher than the
minimum safe water level. When a
LWCO is installed, it must be wired
back to the appropriate terminal on the
boiler PC Board.
•
Water Fill Valve
—
Maintains proper
water pressure in the central heating
circuit.
•
Back Flow Preventer
—
Use a back
flow preventer in the filling circuit to
the appliance as required by local code.
•
Dirt Trap
—
Protects the boiler from
debris in the plumbing system.
Heating Supply Connection
Содержание I Series
Страница 124: ...124 Rinnai I Series Condensing Boiler Combi Manual ...
Страница 125: ...Rinnai I Series Condensing Boiler Combi Manual 125 ...
Страница 134: ...134 Rinnai I Series Condensing Boiler Combi Manual ...
Страница 135: ...Rinnai I Series Condensing Boiler Combi Manual 135 ...
Страница 136: ...136 Rinnai I Series Condensing Boiler Combi Manual 800000111 3 2019 ...