Connect flue system
Consult the Rinnai Arriva and Evolve flue installation guide supplied with the Arriva/
Evolve flue kits for detailed flue installation instructions. For connection of the flue
to the heater refer information below.
Removing the pipe clamp, extension tube and exhaust pipe
Before installing the heater into the enclosure the pipe clamp, telescopic extension tube, and
exhaust pipe need to be removed so there is room to connect the flue system.
1. Undo the pipe clamp and remove the telescopic extension tube from the exhaust pipe.
2. Secure the telescopic extension tube to the flue system with the exhaust pipe lock.
3. Attach the air hose to the flue transition and secure with the cable tie provided.
Please note that in the adjacent image in step 4 the air hose is already connected to the flue. It is
much easier to connect the air hose to the unit than to connect the air hose to the flue once the
heater is in place. Ensure the air intake hose of the heater is properly secured to the air connection
on the flue system using the cable tie provided, and that the rubber seal is placed on the unused
air intake connection.
Flue slide stopper
Flue transition (ASPDFK, EVOKIT03)
The flue transition provides a connection between the flue system and the heater’s flue spigot and
air intake. For all flueing installations, except horizontal direct flueing, the flue transition is counted
as a 90 ° bend. The flue transition requires a 5 mm clearance from combustibles. This clearance
is provided automatically when the supplied standoff brackets are used. All other flue components,
except the elbow section of the EVOKIT03, are designed for zero clearance and can be placed
hard against timber or plasterboard.
The exhaust pipe lock is provided with the ASPDFK and EVOKIT03 flue kits
Flue transition outlet
Unused air intake
Air intake
Wall terminal
ASPDFK
ASPKIT03/EVOKIT03
Elbow component is
counted as a 90° bend