14
(4)
Alarm contact
・Alarm contacts shall be used only for external buzzer and alarm light, and do not use it for the controlling
use (such as solenoid valve control etc).
When control the external load, the bad influence may be given to the system according to the load
characteristics. In such case, the following countermeasure shall be taken to stabilize the action and
protect the contents.
・Relayed by the low voltage relay and operate by connecting CR circuit (Spark Killer: SK) (Diode etc for
DC) suited for relay coil directly to relay.
・Add CR circuit to the load side of relay on the request.
Reference: By the condition of load, CR circuit may be better to install in the contact side but it is required
to put in by checking the action of load.
SK:Surge absorption filter
-How to think alarm contacts against inductive load-
The spec for alarm contact of OX-591 is described by the conditions of resistive load.
When use the inductive load for alarm contacts, the very high reverse electromotive voltage may be
generated and the following trouble tends to be produced.
・Contact part of relay is melted adhesively and the contacts can not be activated.
・High voltage is put inside of indicator/alarm unit and then, electrical parts may be damaged.
・As it is big noise, the trouble action may be taken by the reckless drive of CPU.
・Irrespective of inductive load, there is the possibility of unforeseeable noise instruction for contact.
Above trouble may be generated.
V
SK
L
o
ad
V
SK
C
o
il
Power supply
Power supply
Relayed relay
(Low voltage relay)
Alarm contact
OX-591
CAUTION
(FOR USE OF NORMALLY-CLOSED CONTACT)
Normally-closed contact (Break contact) at non-existing condition may change to open contact in a
moment due to physical shock.
Whenever alarm signals from gas detectors are used with normally-closed contact, please put
delayed-circuit (for about one second) to receiver side of normally-closed contact to avoid such
phenomenon.
Содержание OX-591
Страница 1: ...PT1E 0899 FOR USERS OPERATING INSTRUCTION MANUAL FOR INDICATOR ALARM UNIT OX 591 ...
Страница 5: ......
Страница 6: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 19: ......
Страница 20: ......
Страница 21: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 26: ......
Страница 27: ......
Страница 36: ......