8
4−4.How to install
(1)
Mounting to the wall surface
Mount the detector head to a flat surface (wall
surface, etc) with either M6 bolts or M10 bolts
through mounting holes. Refer to 「3-1. External
drawing」 for mounting pitch.
(2)
Mounting to the pole
The unit can be mounted to the pole (2B pipe)
by using the optional U-bolts shown in right
figure.
(3)
Installation to the outdoors
For outdoor installation, optional drip-proof cover
is required to keep reliable detection although this
is a drip-proof design. Contact RIKEN KEIKI Co.,
Ltd.
4−5.Caution at wiring construction
4−6.Applicable cable
Signal transmission
: CVVS 1.25mm
2
, 2C or equivalent
Transmission distance : Within 600m at full lengths
Cable O.D.
: φ8-φ11mm
4−7.Example of cable connection
(1) In case of non-explosion proof system
① Lead the applicable cable through cable inlet
and connect to the terminal strip.
② Connect the other side of the cable to the
indicator/alarm unit side.
③ Connect the shieldʼs drain ground on the
indicator/alarm unit side.
・When make wiring construction, take care not to damage the internal electronics circuit.
・When handle the detector unit, put it at horizontal position. If put it vertically, it tends
to fall and damage the detector.
・Power cable and signal cable shall not be laid down together with motive power cable
such as motor, etc.
・When use twisted cable, take care not to contact a part of core cable with other core
cable.
CAUTION
!
ケーブルの接続
ケーブル
−
+
端子台
センサ
リード線
Sensor lead
wire
Terminal
strip
Cable connection
Mounting to the pole
2B pipe
(
O.D. 60.5mm
)
U-bolt
(
Nominal
diameter 50B
)
Cable