6 Maintenance
6-2. Calibration method
- 24 -
6-2. Calibration method
Perform a calibration with the indicator/alarm unit (zero adjustment/span adjustment mode) using the
calibration gas.
Zero adjustment gas
Calibration gas (collected in a gas sampling bag)
Gas sampling bag for exhaust gas
Check and adjustment are performed at the indicator/alarm unit side. See the operating manual of the
indicator/alarm unit for details.
(1) Zero adjustment
Adjust the reading to zero at the indicator/alarm unit side under the condition that no gas is present around
the detection point.
If a gas is present around the detection point, collect fresh air in a gas sampling bag or the like and release it
at the detection point for two minutes or so before starting the zero adjustment.
≪
GD-A80-70
≫
Calibration adapter
Pump
Flow meter
Gas
sampling
bag
Needle valve
Exhaust air
WARNING
When the zero adjustment is performed in the atmosphere, check the atmosphere for
freshness before beginning the adjustment.
If interference gases exist, the calibration cannot be performed properly, thus leading to
dangers when the gas leaks.