4 How to Use
4-3. Precautions for system designing
- 14 -
Protection against
lightning
Take appropriate measures in accordance with the importance of the facilities and
the environment.
Provide protection by a lightning arrester (cable arrester).
(Although inductive lightning surge can be transmitted through the cable, it is
prevented by installing a lightning arrester before the field devices and central
processing equipment. For information on how to use a lightning arrester,
please contact the manufacturer.)
Grounding
In addition to lightning, there are more sources of surge noise. To protect units
from these noise sources, the units must be grounded.
* The lightning arrester has a circuit to remove a surge voltage which damages field devices, so that
signals may be attenuated by installing the arrester. Before installing a lightning arrester, verify
that it works properly.