4 How to Use
4-5. How to wire
RM-6000
- 22 -
Compatible bar terminal
For a bar terminal, the following items are available.
・
Bar terminal (ferrule): Model 216 Series
(manufactured by WAGO)
・
Crimping tool: Model VarioCrimp 4 (206-204)
(manufactured by WAGO)
<How to Connect to Terminal Plate>
When cables are connected to the terminal plate, use the dedicated screwdriver or a compatible flathead
screwdriver to do so as shown below.
■
Wiring: Perform wiring as shown in the figure below.
(1) Push the push button straight downward using the
compatible screwdriver or equivalent to open the
spring.
(2) Insert a wire with a specified bare wire length until the
end of it reaches the deepest point.
(3) The wire will be connected when the screwdriver is
released.
CAUTION
The specified bare wire length must be observed when the wire insulation is peeled off.
Improper clamping of the wire due to a shorter bare wire length may cause defective electric
conduction or heating.
Catching the wire insulation due to a shorter bare wire length may cause defective electric
conduction or heating.
Exposing the wire due to a longer bare wire length may cause defective insulation or a short circuit.
Be careful not to break up the wire. If the wire is broken up when inserted to the terminal, this may
cause defective insulation or heating.
8 - 9 mm
CAUTION
A bar terminal of the specified model must
be used. Using other bar terminals
invalidates the warranty of the performance.
CAUTION
The right tools must be used. Do not insert more than one wire into one wiring hole. Even if
the total size (mm
2
) of two or more wires is within the maximum wire connection range of the
terminal plate, it may cause reduced spring clamping force, defective insulation due to clogged wire
sheath, defective contact or coming off of wires.