236
(continuous light), or reset Q with off delay. Output Q can
be reset with a signal at the Trg input.
Input
R
You set the current time Ta, and reset the output to 0, with
a signal at input R.
Parameter
T:
The output is reset (1 to 0 transition) when the time T
has expired.
T
L
determines the period during which the input must be
set in order to enable the permanent light function.
T
!
Determines the on delay for the pre-warning time.
T
!L
determines the length of the pre-warning time.
Retentivity
set (on) = the status is retentive in memory.
Output
Q
Output Q is set with a signal at input Trg, and it is reset
again after a configured time has expired and depending
on the pulse width at input Trg, or it is reset with another
signal at input Trg.
Parameter
The off-delay time T, the permanent light time TL, the on-delay pre-warning time T!, and the pre-warning
time period T!L can be provided by the actual value of another already-programmed function:
Analog comparator: Ax – Ay
Analog trigger: Ax
Analog amplifier: Ax
Analog multiplexer: AQ
Analog ramp: AQ
Analog math: AQ
PI controller: AQ
Data latching relay: AQ
Up/Down counter: Cnt
The value of
"T","TL"
can be set/modified in parameter mode.
Timing diagram
Description of the function
Содержание EXM-12DC-DA-R-HMI
Страница 15: ...15 Application 2 Home Security Application 3 Remote monitoring of product level in a tank...
Страница 32: ...32 Note This command is only for 2G version unit it is unavailable for 4G version unit MsgI01 MsgI02...
Страница 35: ...35 How to change the phone book include phone number and Email address Only for 4G version...
Страница 38: ...38...
Страница 49: ...49 Step C Download voice section Click menu Tool Record Click Hardware Detect button...
Страница 66: ...66 You can read the parameters from the PLC...
Страница 68: ...68...
Страница 75: ...75 Modbus Poll works as TCP client...
Страница 78: ...78 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Страница 79: ...79 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Страница 80: ...80 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Страница 84: ...84 3 Click Read button to read web server configure The default configuration is as follows...
Страница 102: ...102 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Страница 103: ...103 Slave3 IP 192 168 0 103 TCP server port 8003 Step 2 Program in master and slave...
Страница 115: ...115 Slave1 IP 192 168 0 101 UDP Server port 8001 Slave2 IP 192 168 0 102 UDP Server port 8002...
Страница 116: ...116 Slave3 IP 192 168 0 103 UDP Server port 8003 Step 2 Program in master and slave Master program...
Страница 128: ...128 Network settings You can view the network parameters in such table...
Страница 135: ...135 3 Select Ethernet option 4 To search PLC s IP by clicking Search button...
Страница 143: ...143 B001 Transfer the I1 I4 status from the master to the Q1 Q4 of the slave1 Setting as follows...
Страница 144: ...144 B002 Transfer the I1 IA status from the master to the Q1 QA of the slave2 Setting as follows...
Страница 145: ...145 B005 Read the I1 I4 status from the slave1 to the F11 F14 of the master Setting as follows...
Страница 146: ...146 B006 Read the I1 IA status from the slave2 to the F21 F24 of the master Setting as follows...
Страница 147: ...147 B009 Read the AF1 value from the slave1 to the AF1 of the master Setting as follows...
Страница 148: ...148 B010 Read the AF1 value from the slave2 to the AF2 of the master Setting as follows...
Страница 156: ...156 Manual programming menu How to program via keypad Please refer to the chapter 5 for more detail...
Страница 259: ...259 C Analog input value of ELC 12 CPU and extensions D Analog output value of CPU and extensions...
Страница 260: ...260 E F digital flag status F AF analog flag value...
Страница 261: ...261 G M status H AM value...
Страница 263: ...263 C Press ok for 3 seconds and enter into edit mode D Modify value by pressing arrow keys and confirm with OK key...
Страница 332: ...332 For example If the Memory Read block had been triggered the Q1 of ELC 12 CPU will be set 1...
Страница 359: ...359 6 5 52 Comparison of 2 values Short Description The COMPARE function is used to compare two analog values...
Страница 395: ...395 Right click Q2 and then click Set Output State Click OK button and the Q2 of x Messenger will be turned off...
Страница 398: ...398 4 Click to transfer data into one excel file it contains AI1 AQ number value and the corresponding time...
Страница 411: ...411 Establish the communication between eSmsConfig and EXM WIFI Unit...
Страница 412: ...412 Two communication modes available A EXM WIFI unit works as server eSmsConfig works as client...
Страница 413: ...413 B EXM WIFI unit works as client eSmsConfig works as server eSmsConfig com settings Web page settings of wifi module...
Страница 422: ...422 The default settings of HF A11 is closed if you want to use the LAN port please select open AP setting item STA item...
Страница 426: ...426 7 6 How to configure WIFI connection TCP protocol among EXM WIFI CPUs...
Страница 430: ...430 B001 Transfer the I1 I4 status from the master to the Q1 Q4 of the slave1 Setting as follows...
Страница 431: ...431 B002 Transfer the I1 IA status from the master to the Q1 QA of the slave2 Setting as follows...
Страница 432: ...432 B005 Read the I1 I4 status from the slave1 to the F11 F13 of the master Setting as follows...
Страница 433: ...433 B006 Read the I1 I4 status from the slave2 to the F21 F23 of the master Setting as follows...
Страница 434: ...434 B009 Read the AF1 value from the slave1 to the AF1 of the master Setting as follows...
Страница 435: ...435 B010 Read the AF1 value from the slave2 to the AF2 of the master Setting as follows...
Страница 436: ...436...