217
When 0.02 % of the time T is smaller than 0.02 seconds, the maximum deviation is 0.02 seconds.
Example:
The maximum tolerance per hour (3600 seconds) is ±0.02%, which is proportional to ± 0.72
seconds. The maximum tolerance per minute (60 seconds) is ± 0.02 seconds.
Accuracy of the timer (weekly/yearly timer)
The maximum timing in accuracy is ± 5 s/day.
6.4.3 Backup of the real-time clock
Because the internal real-time clock of an x-Messenger is backed up, it continues operation after a power
failure. The ambient temperature influences the backup time. At an ambient temperature of 25°C, the typical
backup time of x-Messenger is 100 hours.
6.4.4 Retentivity
The switching states and counter values of SFs can be set retentive. This means that current data is retained
after a power failure, and that the block resumes operation at the break point. The timer is not reset, but
resumes operation until the time-to-go has expired, for example, to enable this response, however, the
relevant functions must be set retentive.
R: The data is retained.
/: Current data is not retained (default). See the section in topic "Second circuit program
" on enabling and disabling retentivity.
SFs hours counter, weekly timer, yearly timer and PI controller are always retentive.
6.4.5 Parameter protection
In the parameter protection settings, you can determine whether or not the parameters can be displayed and
edited in x-Messenger parameter assignment mode. Two options are available:
+: The parameter attribute permits read/write access in parameter assignment mode(default).
-: The parameter settings are read–/write–protected in parameter assignment mode, and can be edited
only in programming mode. See the parameter protection mode example in the "Second circuit program".
6.4.6 Calculating the gain and offset of analog values
A sensor is connected to the analog input and converts a process variable into an electrical signal. This value
of signal lies within the typical range of this sensor. x-Messenger always converts the electrical signals at the
Содержание EXM-12DC-DA-R-HMI
Страница 15: ...15 Application 2 Home Security Application 3 Remote monitoring of product level in a tank...
Страница 32: ...32 Note This command is only for 2G version unit it is unavailable for 4G version unit MsgI01 MsgI02...
Страница 35: ...35 How to change the phone book include phone number and Email address Only for 4G version...
Страница 38: ...38...
Страница 49: ...49 Step C Download voice section Click menu Tool Record Click Hardware Detect button...
Страница 66: ...66 You can read the parameters from the PLC...
Страница 68: ...68...
Страница 75: ...75 Modbus Poll works as TCP client...
Страница 78: ...78 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Страница 79: ...79 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Страница 80: ...80 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Страница 84: ...84 3 Click Read button to read web server configure The default configuration is as follows...
Страница 102: ...102 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Страница 103: ...103 Slave3 IP 192 168 0 103 TCP server port 8003 Step 2 Program in master and slave...
Страница 115: ...115 Slave1 IP 192 168 0 101 UDP Server port 8001 Slave2 IP 192 168 0 102 UDP Server port 8002...
Страница 116: ...116 Slave3 IP 192 168 0 103 UDP Server port 8003 Step 2 Program in master and slave Master program...
Страница 128: ...128 Network settings You can view the network parameters in such table...
Страница 135: ...135 3 Select Ethernet option 4 To search PLC s IP by clicking Search button...
Страница 143: ...143 B001 Transfer the I1 I4 status from the master to the Q1 Q4 of the slave1 Setting as follows...
Страница 144: ...144 B002 Transfer the I1 IA status from the master to the Q1 QA of the slave2 Setting as follows...
Страница 145: ...145 B005 Read the I1 I4 status from the slave1 to the F11 F14 of the master Setting as follows...
Страница 146: ...146 B006 Read the I1 IA status from the slave2 to the F21 F24 of the master Setting as follows...
Страница 147: ...147 B009 Read the AF1 value from the slave1 to the AF1 of the master Setting as follows...
Страница 148: ...148 B010 Read the AF1 value from the slave2 to the AF2 of the master Setting as follows...
Страница 156: ...156 Manual programming menu How to program via keypad Please refer to the chapter 5 for more detail...
Страница 259: ...259 C Analog input value of ELC 12 CPU and extensions D Analog output value of CPU and extensions...
Страница 260: ...260 E F digital flag status F AF analog flag value...
Страница 261: ...261 G M status H AM value...
Страница 263: ...263 C Press ok for 3 seconds and enter into edit mode D Modify value by pressing arrow keys and confirm with OK key...
Страница 332: ...332 For example If the Memory Read block had been triggered the Q1 of ELC 12 CPU will be set 1...
Страница 359: ...359 6 5 52 Comparison of 2 values Short Description The COMPARE function is used to compare two analog values...
Страница 395: ...395 Right click Q2 and then click Set Output State Click OK button and the Q2 of x Messenger will be turned off...
Страница 398: ...398 4 Click to transfer data into one excel file it contains AI1 AQ number value and the corresponding time...
Страница 411: ...411 Establish the communication between eSmsConfig and EXM WIFI Unit...
Страница 412: ...412 Two communication modes available A EXM WIFI unit works as server eSmsConfig works as client...
Страница 413: ...413 B EXM WIFI unit works as client eSmsConfig works as server eSmsConfig com settings Web page settings of wifi module...
Страница 422: ...422 The default settings of HF A11 is closed if you want to use the LAN port please select open AP setting item STA item...
Страница 426: ...426 7 6 How to configure WIFI connection TCP protocol among EXM WIFI CPUs...
Страница 430: ...430 B001 Transfer the I1 I4 status from the master to the Q1 Q4 of the slave1 Setting as follows...
Страница 431: ...431 B002 Transfer the I1 IA status from the master to the Q1 QA of the slave2 Setting as follows...
Страница 432: ...432 B005 Read the I1 I4 status from the slave1 to the F11 F13 of the master Setting as follows...
Страница 433: ...433 B006 Read the I1 I4 status from the slave2 to the F21 F23 of the master Setting as follows...
Страница 434: ...434 B009 Read the AF1 value from the slave1 to the AF1 of the master Setting as follows...
Страница 435: ...435 B010 Read the AF1 value from the slave2 to the AF2 of the master Setting as follows...
Страница 436: ...436...