FAN SPEED CONTROL ADR 80 - 230   

 

ADR80230_5.04_eng

 Project: 

ADR Regulator

 

Revision Doc.:5,0 

Date

: 29.05.2009

 Page.

 4

 

 

Key 3 

Function description 

Remarks and state of the adjustment 

PROG  

Key3 

 

Access at programming of SET parameters

  

 Access at set parameters 

3° 

Modifies the SET of adjustment  

1° - only if adjustment is OFF 
2° - also during the operation of the regulator 
3° - also during the operation of the regulator 

 

Key 4 

Function description 

Remarks and state of the adjustment 

END 

 

 Confirms any change of the program-

ming, and exits.  

 Sensor values display 

Valid for any mode of the regulator – either in the 
OFF position or for changes during operation. 
Also during the working of the adjustment 

 

3.1 The function of curser an arrow 

 

Î

 

The cursor indicates the position to be reached, pushing the PROG key again 

Ï

The arrow on the right position of display indicates that the UP key returns to the preceding posi-
tion 

Ð

The arrow on the right position of display indicates that the DOWN key goes to the next position 

Ú

 

The double arrow indicates that it is possible to modify the SET or the function with keys 1 or 2 

 

Green LED – Voltage  Red LED - Alarm

 

 

4.0 SETUP PARAMETERS AND ADJUSTMENT FUNCTIONAL PARAMETERS

 

Programming of the device is made by two systems of parameters, the Set-up and the programming. SETUP 
parameters do not require programming during normal operation of the adjustment, but determines how the 
regulator works. 
Programming parameters determine the real response of the system during adjustment. Listed below are pa-
rameters followed by the default settings. 

 

4.1  SETUP PARAMETERS 

Programming of the SETUP is possible only when the regulator is off. In this position pushing the 3 PROG key 
displays the main MENU as follows: 
 

Î

  S 

           

SETUP 

parameters 

 

 Adjustment parameters 
 Language field 

  R E G U L  A T I  O  N   

 

 

 

 

  L  A N G U A G E  

 

 

 

 

 

 

 
Pushing again the key 3 PROG the display shows the frame to modify the first Set-up parameter 
 

Î

  P  O  W  E  R  S  U  P  P  L  Y   

 

 

 

Selects the card supply voltage (230V or 400V). 

  S I  N G L  E P H A S E      

Ú

 
With the arrow keys it is possible to display the next windows for parameters set, as described below 

Î

  R 

I O 

     Selects 

the 

adjustment 

system 

with: 

TEMPERATURE, PRESSURE, VOLT 

 

I  N   

 

 

P  R  E  S S U R E  

Ú

 

WORKING IN TEMPERATURE 

Working in TEMPERATURE requires the use of NTC10K type sensors. 
This mode automatically stops the display of windows related to pressure or volt adjustment. 

WORKING IN VOLT 

When working in VOLT a signal coming from an external adjustment source must be already present. 
The input signal is 0 – 10 V.  
Modify        

SET - Point  

 

impossible 

Set           

SET - Adjustment 

impossible

  

Display: display of the measured value given in VOLT

 

 

Содержание MicroNova ADR 230 DP

Страница 1: ...ion Doc 5 0 Date 29 05 2012 Page 1 CONDENSATION SPEED ADJUSTMENT ADR 230 ADR 80 DP Display D LCD PMK Transducer NTC Sensor Room outdoor Sensor FAN SPEED CONTROLLER Pressure Temperature or externally controlled for three phase and single phase Induction motors SERIES ADR 80 230 ...

Страница 2: ...nts using one sensor 7 4 4 Connection and setup with 1 or 2 sensors 8 5 ADR80 230 with external control SPS 9 5 1 ADR80 230 with external control and 0 10V signal 9 5 2 ADR80 230 with external control and 0 20 mA signal 9 5 3 Minimum speed 9 5 4 Maximum speed 9 7 0 System Master and Slave 10 8 0 Wiring diagram ADR80 230 with pressure transducer PMK 11 9 0 Display 11 1 Standard display ADR in OFF 1...

Страница 3: ...Function description Note ON OFF ON OFF of card and therefore of OUTPUT CONTROL FUNCTION ON running adjusted output voltage changed OFF stop of voltage change function Î 1 function when selected allows the in crease of the value or moves the menus towards the top 2 function with the card ON pressing key 3 modifies the SET towards the top The 1 function is activated even if the set is in ON positio...

Страница 4: ...s made by two systems of parameters the Set up and the programming SETUP parameters do not require programming during normal operation of the adjustment but determines how the regulator works Programming parameters determine the real response of the system during adjustment Listed below are pa rameters followed by the default settings 4 1 SETUP PARAMETERS Programming of the SETUP is possible only ...

Страница 5: ...tor starts automatically M A I N S Y E S Ú Î S E N S O R S N R Defines the number of sensors transducers connected It could be 1 or 2 T R A N S D U C E R S 1 Ú Î O U T P U T P H A S E Defines the minimum supply voltage in for the fan A minimum supply voltage for all the fans of about 15 of the total voltage is available M I N I M U M 0 Ú Î O U T P U T P H A S E Defines the maximum supply voltage o...

Страница 6: ...n enlarged the ADR 80 and 230 can be accessed in 5 languages German English Italian French and Spanish S E T U P P A R A M E T Place the cursor on the line Language and confirm the selection with the PROG key Î R E G U L A T I O N L A N G U A G E Î E N G L I S H Place the cursor on the selected language and con firm the selection with the PROG key The language is automatically changed Push END and...

Страница 7: ...erature via temperature sensors NTC Attention Do not forget to place the correct jumper according to the sensor 6 4 3 Wiring and placing jumpers for 2 set point but one sensor only Attention Bypass connection has to be made potential free no voltage Depending to the sensor input Jumper have to be placed Please consider for 1 sensor with 2 set points with open Bypass SET1 control is fixed by set po...

Страница 8: ...mperature of circuit 1 or 2 Bypass SET 1 remains open Control with 2 Set points Setting in 2 Sensors SETUP 2 Set point Signals of circuit 1 and 2 will be used in accordance if Bypass is open or closed Bypass can be opened or closed by timer switch Thermostat or any other device potential free Bypass open SET 1 Circuit 1 takes over control Bypass closed SET2 Circuit 2 takes over control Attention B...

Страница 9: ...e via remote control D LCD When the Minimum speed of the Setup falls below the setting the connected Motor will be cut off This happens even when the external control still calls for speed 6 5 4 Maximum Speed By using an external control for ADR with 0 10 V and 0 20 mA signals it is possible to limit the maxi mum speed too When the maximum speed is reached the internal control of the ADR 80 230 li...

Страница 10: ...rature sensor jumpers have to be placed see drawings below 7 1 Signal 0 10 V Slave with jumpers 7 2 Signal 4 20 mA Slave without jumpers 7 3 Signal NTC Slave without jumpers Attention Valid for all Slave Versions Slave never to be connected to 12 To further ADR controller Master Slave Slave mA V NTC JP1 IN1 mA V NTC JP2 IN1 IN2 12 GND BY PASS ADR 80 230 V I N V I N mA V NTC JP1 IN1 mA V NTC JP2 IN...

Страница 11: ...ration 9 3 Sensor value display During operation it is possible to check the values measured by the sensors This function works as a manometer and gives the pressure temperature values of each connected circuit S E N S O R N 1 R 2 2 3 9 6 C 1 5 2 B A R 9 4 By Pass adjustment On the board there is one input available which excludes adjustment In this case the fans will work without adjustment and t...

Страница 12: ... fan Sector 3 Temperature or Pressure between Set Proportional Range and Set Proportional Range Supply voltage in creases proportional between the minimum and the maximum Sector 4 Temperature or Pressure between Set Proportional Range and Max Fan supply voltage equal to the maximum set voltage Sector 5 Temperature or Pressure higher then Max Max fan supply voltage 400V 230V 460 Note The transition...

Страница 13: ... installation ventilation recommended 12 5 LCD Display D LCD Dimensions CN1 CN2 R S T W V U CN3 ADR 80 R S T M 3 M 1 R S T 400 VAC 230 VAC Max 8 A ADR 80 M 3 CN1 CN2 CN3 W T V S U R CN7 400VAC R S T ADR 230 M 1 CN1 CN2 CN3 W T V S U R 230VAC S T ADR 230 400 VAC 230 VAC Max 23A Max 23A 270 230 150 270 230 90 Fuses 1 x F630 mA 250 Vac 6 3 x 32 mm 1 x F630 mA 250 Vac 5 x 20 mm 51 mm 167 mm 58 mm 51 5...

Страница 14: ...per correctly No info in Display of remote control dark or unreadable signs Remote control Display or ADR controller defect Change Display or ADR board Pressure on Display not analog to pressure gauge Manometer Wrong max pressure set in Setup Wrong refrigerant set in Setup Correct setting of maximum pressure according to the used pressurer tranducer or correct refrigerant ADR switches off despite ...

Страница 15: ...he serial port of the ADR it is not possible any longer to connect the ADR to a network with modem etc The ADREX board ZPK01 is supplied with a short connecting cord to serial port ADR and Plastic mounting holder ADREX is compatible to safety regulation IP 22 ADREX for ADR 80 230 ADR EX INPUT Remote control ADR EX OUTPUT RELAY Warning signal Contact Function Setting I O O I O C CO Common CO NA CO ...

Страница 16: ...FAN SPEED CONTROL ADR 80 230 ADR80230_5 04_eng Project ADR Regulator Revision Doc 5 0 Date 29 05 2009 Page 16 ...

Страница 17: ...FAN SPEED CONTROL ADR 80 230 ADR80230_5 04_eng Project ADR Regulator Revision Doc 5 0 Date 29 05 2009 Page 17 ...

Отзывы: