13.1 What you should know by rating and designing a speed controller

 

 

To be watched 

Reason 

To do 

Higher current in part load operation 
 

In part load operation in relation to 
the used fan motor higher currents 
will be measured. These currents 
are mostly higher than data printed 
on machine plate of motor 

Ask Motor Manufuturer for current when used with TRIAC control. 
If not possible calculate about 20 % as security on top of the current written on the 
motor plate 
By pratical expierience motors have been found with 30% higher current as written 
on motor 
This has to be considered also by rating overload protectors and fuses 

Wrong signal and measured data 

Close locations of signal lines 
along power lines or contactors 
lead to wrong signals to the 
controller 

Signal line should be isolated and/or seperatly installed away from power lines 

To save motor and controller it is 
recommended to use overload 
protectors and/or fuses 
 

Since ADR controller do have a 
wide range of current there is no 
chance to protect the controller 
itself against short circuits in power 
supply or motor 

A protection against high current or short circuits is not obligatory. But it protects 
motor and speed controller in case of power supply problems and short circuits from 
motor side.  

Chosing an ADR speed controller 

Watch higher currents in part load 
operation 

By chosing the size of a speed controller take higher currents in part load conditions 
into your calculation. If you do not have data from the motormanufacturer add 15-20 
% on top of the max current mentioned on the motor plate. 

 

13.2 Alarm Management 

A number of alarms are displayed. The display shows the type of alarm and gives an indication of the problem. 
The table below shows the alarms displayed, the action at the fan adjustment and the reason of the fault. 

 

Alarm  

Reason 

To do 

ALARM PHASE 
POWER SUPPLY

 

 Wrong Voltage 

  No funktion of controller 

  Press OFF Key and with PROG Key  correct setting of 

Voltage  

 

ALARM PROBE 1 / 2  
ERROR

 

  Signal line broken 

  Over or under Limit   

  Sensor (Probe) defekt,  

  Sensor connections wrongly installed    

  Jumper below the 8 pole (green) Terminal wrongly placed 

  Change signal line 

 Change settings. 

 Change Sensor 

  Check connections on sensor and controller side  

  Place Jumper correctly 

No info in Display of remote 
control (dark or unreadable 
signs 

   Remote control(Display) or ADR controller defect 

 
 

   Change Display or ADR board  

Pressure on Display not 
analog to pressure  gauge  
(Manometer) 

  Wrong max .pressure set in Setup 

  Wrong refrigerant set in Setup 

  Correct setting of maximum pressure according to the used 

pressurer tranducer or correct refrigerant 

ADR switches off despite of 
demand from system 

  Signal line not isolated and to close install to power lines and 

Contactors. Tolerance of ADR exceeded 

  Caused by Interference in industrial  and commercial areas  

  Close to train and Metro stations and its power supply lines 

  Seperate signal line from power lines and contators and 

isolate signal lines  

  Use Filter (Ferrit) in power supply per line to ADR 

Display 0%  
Motor still running

 

  There is a very little current from signal line or external control 

existing  

  Minimum speed to be set from 0 % to 5-10 %   

This extends the lif expectancy of the motor and switchs it off 
when no demand. 

Elektro magnetic noise  
during part load operation

 

 
 

  Slow motion fan units in particular with large diameters could 

cause electro magnetic noise when running at low speed. In 
addition at low speed a resonance in the surrounding area 
could occur. 

 

  In many cases an increase to a minimum speed of 5-10% will 

solve the problem 

  The use of a noise filter in connection with capacitors in each 

line is a final and one of the best solutions 

Running- and vibration noise  
 

  Fan units, even when speed controllable, are mainly balanced 

and optimised for full speed.. At low speed vibrations could 
appear which are  

    reinforced by resonance. 

  Carry out a test to find Minimum speed under which vibration 

noise stops. Set Minimum speed..  

  Start fan motor always with full speed for 2-3 seconds. It 

overrides the critcal speed within a short time. 

 

 

14.1 Technical Data and Limits 

 
Power supply

 

230/400V ( - 15% + 15%) Single and three phase defined in setup by remote control (D-LCD) 

Frequenzy: 

50 or 60 Hz  +/- 2%, automatic recognition trough Software 

Cos phi motor

 

Automatic recognition through Software and adjustment of control characteristics 

Installation, Safety class

 

Model ADR 80 and 230 for cabinet installation, Safety class IP 20 

 

 

 

Cabinet ventilation recommended to compensate a heat generation of total ca. 4.5 Watt per Ampere. 

Operating conditions 

 

 –18°C to +50°C ambient temperature, relative Humidity max. 85% not condensing. 

 

 

 

Remote control Display LCD: Lowest temperature 0°C, because of visibility in LCD Display. 

Overload/Starts per hour  

        

2 x max. amps for 20 seconds, 30 Starts per hour 

 

 
 
 
 

 
 

Содержание MicroNova ADR 230 DP

Страница 1: ...ion Doc 5 0 Date 29 05 2012 Page 1 CONDENSATION SPEED ADJUSTMENT ADR 230 ADR 80 DP Display D LCD PMK Transducer NTC Sensor Room outdoor Sensor FAN SPEED CONTROLLER Pressure Temperature or externally controlled for three phase and single phase Induction motors SERIES ADR 80 230 ...

Страница 2: ...nts using one sensor 7 4 4 Connection and setup with 1 or 2 sensors 8 5 ADR80 230 with external control SPS 9 5 1 ADR80 230 with external control and 0 10V signal 9 5 2 ADR80 230 with external control and 0 20 mA signal 9 5 3 Minimum speed 9 5 4 Maximum speed 9 7 0 System Master and Slave 10 8 0 Wiring diagram ADR80 230 with pressure transducer PMK 11 9 0 Display 11 1 Standard display ADR in OFF 1...

Страница 3: ...Function description Note ON OFF ON OFF of card and therefore of OUTPUT CONTROL FUNCTION ON running adjusted output voltage changed OFF stop of voltage change function Î 1 function when selected allows the in crease of the value or moves the menus towards the top 2 function with the card ON pressing key 3 modifies the SET towards the top The 1 function is activated even if the set is in ON positio...

Страница 4: ...s made by two systems of parameters the Set up and the programming SETUP parameters do not require programming during normal operation of the adjustment but determines how the regulator works Programming parameters determine the real response of the system during adjustment Listed below are pa rameters followed by the default settings 4 1 SETUP PARAMETERS Programming of the SETUP is possible only ...

Страница 5: ...tor starts automatically M A I N S Y E S Ú Î S E N S O R S N R Defines the number of sensors transducers connected It could be 1 or 2 T R A N S D U C E R S 1 Ú Î O U T P U T P H A S E Defines the minimum supply voltage in for the fan A minimum supply voltage for all the fans of about 15 of the total voltage is available M I N I M U M 0 Ú Î O U T P U T P H A S E Defines the maximum supply voltage o...

Страница 6: ...n enlarged the ADR 80 and 230 can be accessed in 5 languages German English Italian French and Spanish S E T U P P A R A M E T Place the cursor on the line Language and confirm the selection with the PROG key Î R E G U L A T I O N L A N G U A G E Î E N G L I S H Place the cursor on the selected language and con firm the selection with the PROG key The language is automatically changed Push END and...

Страница 7: ...erature via temperature sensors NTC Attention Do not forget to place the correct jumper according to the sensor 6 4 3 Wiring and placing jumpers for 2 set point but one sensor only Attention Bypass connection has to be made potential free no voltage Depending to the sensor input Jumper have to be placed Please consider for 1 sensor with 2 set points with open Bypass SET1 control is fixed by set po...

Страница 8: ...mperature of circuit 1 or 2 Bypass SET 1 remains open Control with 2 Set points Setting in 2 Sensors SETUP 2 Set point Signals of circuit 1 and 2 will be used in accordance if Bypass is open or closed Bypass can be opened or closed by timer switch Thermostat or any other device potential free Bypass open SET 1 Circuit 1 takes over control Bypass closed SET2 Circuit 2 takes over control Attention B...

Страница 9: ...e via remote control D LCD When the Minimum speed of the Setup falls below the setting the connected Motor will be cut off This happens even when the external control still calls for speed 6 5 4 Maximum Speed By using an external control for ADR with 0 10 V and 0 20 mA signals it is possible to limit the maxi mum speed too When the maximum speed is reached the internal control of the ADR 80 230 li...

Страница 10: ...rature sensor jumpers have to be placed see drawings below 7 1 Signal 0 10 V Slave with jumpers 7 2 Signal 4 20 mA Slave without jumpers 7 3 Signal NTC Slave without jumpers Attention Valid for all Slave Versions Slave never to be connected to 12 To further ADR controller Master Slave Slave mA V NTC JP1 IN1 mA V NTC JP2 IN1 IN2 12 GND BY PASS ADR 80 230 V I N V I N mA V NTC JP1 IN1 mA V NTC JP2 IN...

Страница 11: ...ration 9 3 Sensor value display During operation it is possible to check the values measured by the sensors This function works as a manometer and gives the pressure temperature values of each connected circuit S E N S O R N 1 R 2 2 3 9 6 C 1 5 2 B A R 9 4 By Pass adjustment On the board there is one input available which excludes adjustment In this case the fans will work without adjustment and t...

Страница 12: ... fan Sector 3 Temperature or Pressure between Set Proportional Range and Set Proportional Range Supply voltage in creases proportional between the minimum and the maximum Sector 4 Temperature or Pressure between Set Proportional Range and Max Fan supply voltage equal to the maximum set voltage Sector 5 Temperature or Pressure higher then Max Max fan supply voltage 400V 230V 460 Note The transition...

Страница 13: ... installation ventilation recommended 12 5 LCD Display D LCD Dimensions CN1 CN2 R S T W V U CN3 ADR 80 R S T M 3 M 1 R S T 400 VAC 230 VAC Max 8 A ADR 80 M 3 CN1 CN2 CN3 W T V S U R CN7 400VAC R S T ADR 230 M 1 CN1 CN2 CN3 W T V S U R 230VAC S T ADR 230 400 VAC 230 VAC Max 23A Max 23A 270 230 150 270 230 90 Fuses 1 x F630 mA 250 Vac 6 3 x 32 mm 1 x F630 mA 250 Vac 5 x 20 mm 51 mm 167 mm 58 mm 51 5...

Страница 14: ...per correctly No info in Display of remote control dark or unreadable signs Remote control Display or ADR controller defect Change Display or ADR board Pressure on Display not analog to pressure gauge Manometer Wrong max pressure set in Setup Wrong refrigerant set in Setup Correct setting of maximum pressure according to the used pressurer tranducer or correct refrigerant ADR switches off despite ...

Страница 15: ...he serial port of the ADR it is not possible any longer to connect the ADR to a network with modem etc The ADREX board ZPK01 is supplied with a short connecting cord to serial port ADR and Plastic mounting holder ADREX is compatible to safety regulation IP 22 ADREX for ADR 80 230 ADR EX INPUT Remote control ADR EX OUTPUT RELAY Warning signal Contact Function Setting I O O I O C CO Common CO NA CO ...

Страница 16: ...FAN SPEED CONTROL ADR 80 230 ADR80230_5 04_eng Project ADR Regulator Revision Doc 5 0 Date 29 05 2009 Page 16 ...

Страница 17: ...FAN SPEED CONTROL ADR 80 230 ADR80230_5 04_eng Project ADR Regulator Revision Doc 5 0 Date 29 05 2009 Page 17 ...

Отзывы: