11 The Detector Switching on and Checking

For mounting height 5 m set up DIP-switch «1» to ON position (5 m). If 

the ceiling hight of the room is less than 3 m, it is recommended to set up  
DIP-switch  «1» to OFF position (2.5 m). Thus, the higher sensitivity level is 
provided. It is recommended to use the Detector in this mode in small rooms 
with severe interference conditions.

After enegizing the Detector executes self-testing (checking of power supply, 

environment temperature as well as amplification path testing), the LED blinks 
red (independently from DIP-switch «3» position), output contacts are opened.

During self-testing procedure it is necessary to exclude any movement in the 

detection zone, asi can result in failure message generation.

12 Functional Check

Upon expity «Warm-up Time», the Detector changes to standby mode and is 

able to generate an alarm message.

High filled density of the Detection zone provides to detect intruder moving 

in any direction. Testing and sensitivity adjustment is fulfilled so as to determine 
the detection zone borders.

Testing mode

DIP-switches position: «3» – ON, «2» – ON.
This mode ensures determination of each detection zone beam position. After 

each beam crossing, the indicator switches for 0.25 sec. Optimal movement 
speed at maximal distance is 0.5 m/sec.

Note 

– In this mode  there is no LED indication of аlarm message. 

Under absence of  movement  inside the detection zone, the indicator should 

not light. The testing mode is performed during 5 min, whereafter the Detector 
changes over to «Norm» mode.  

Sensitivity Check

DIP switches position: «3» – ON, «2» – OFF. This mode is intended for the 

Detector sensitivity appraisal (the distance inside the detection zone, which is 
covered before alarm message generation). Alarm message is generated after 
2 – 5 steps inside the detection zone (depending on mounting height and 
direction of movement) during 3 sec.

After each alarm message generation, stop and make a pause till the LED is off, 

after it wait for 8 – 10 sec before proceeding movement inside the detection zone.  

Note 

– In the temperature range near 36 °С, temperature compensation is 

switched on, providing maintainance of detection ability of the Detector.

13 LED Indicator Disabling

For the Detector operation masking, LED indicator disabling mode is provided. 

DIP-switch «3» is in OFF position. In this mode LED is functioning only in first 
minute of operation after the Detector energizing, as well as in modes «Alarm 
memory» and «Failure».

14 Alarm memory

DIP-switch  «4» is ON. The LED is lighting green in 5 min after alarm 

message generation. LED indication duration is 15 min. Change-over of  
DIP-switch «4» from ON to OFF position results in the «Alarm memory» indication 
reset.

15 Self-testing and Failure Indication

The Detector fulfills self-testing automatically, thereby the following parameters 

are checked:

- availability of the receiver and signal amplifier;
- power supply voltage;
- environment temperature.
The Detector  generates «Failure» message with 15 min period under the 

following conditions:

- power supply voltage drop lower than 9.0

-1

 V – by the relay contacts  opening, 

duplicated by perionical single LED indicator blinking green;

- maximal permissible temperature value exceedance – by the relay contacts  

opening, duplicated by perionical twofold LED indicator blinking green;

- negative result of the receiver with signal amplifier testing – by the relay 

contacts  opening, duplicated by perionical threefold LED indicator blinking green.

After removal of the failure cause, the Detector turnes over to the «Standby» 

mode automatically in 15 min. Premature reset of «Failure» LED indication can 
be fulfilled by changing  DIP-switch «2»  position from ON to OFF (or vice versa).

ATTENTION! 

The Detector must be checked at least annually in order to 

test it’s performance.

16 Storage and Transportation 

16.1 The Detectors in their original packing may be shipped by any transport 

means in covered vehicles (in railway, cars, trucks, sealed heated compartments 
of aircraft, ship cargo holds, etc). The storage room should be free from 
current-conducting dust, acid vapors, alkali and gases that cause corrosion 
and destroy insulation.

16.2 The Detectors in their original packing may be stored not more than 3 

months. During this period the Detector package should not have bloodshot 
spots and impurities.

16.3  Upon  the  expiry  of  3  months,  the  Detector  should  be  released  from 

the package. 

17 Manufacturer’s Guarantees

The  Manufacturer  guarantees  conformity  of  the  Detector  to  it’s  Technical 

Specifications if conditions of transportation, storage, assembling and operation 
are observed. The guaranteed storage period is 63 months since the date of 
manufacturing the Detector.

The  guaranteed  period  of  operation  is  60  months  since  the  date  of 

commissioning within the storage period guaranteed.

The Detectors that are found to non-conforming to it’s Technical Requirements 

shall be repaired by the Manufacturer, provided the installation and operation 
rules have been complied with.

18 Acceptance and Packing Certificate

Passive infrared detector «Foton-21»,

serial number ____________, 

has been manufactured in compliance with the active technical documentation 
and classified as fit for operation and packed by «RIELTA» JSC.

Person in charge of acceptance and packing

QC representative_________________    __________________.

day, year, month

Rev. 1 of 25.02.2015

№00117

Made in Russia

«RIELTA» JSC, www.rielta.com,
Chapaeva Str. 17, Saint Petersburg, Russia, 197101, [email protected],
Tel./fax. +7 (812) 233-0302, 703-1360,
Technical support, tel. +7 (812) 233-29-53, 703-13-57, [email protected]

.

Отзывы: