Operation, indications, diagnostic
8.2
Error code list with operation via the control box control panel
Tab. Z
Error
code
Clear text
Possible cause
bAC Er3
Programme module compatibility fault with the base unit dur-
ing the back-up process
The program sequence of the program module is not com-
patible with the base unit
Err PrC
Fault with the program module
–
Error in the data contained in the program module
–
No program module
Loc 2
No flame at the end of the safety time
–
Fuel valves dirty or defective
–
Flame detector dirty or defective
–
Burner not adjusted correctly, no fuel
–
Ignition device defective
Loc 3
Error with air pressure switch (air pressure switch soldered
in position with no load), reduction to specified time (air pres-
sure switch) response time)
Air pressure switch faulty
–
Loss of air pressure signal after the specified time
–
The air pressure switch is soldered in a position without
load
Loc 4
Extraneous light
Burner start-up extraneous light
Loc 5
Air pressure error, air pressure switch soldered in an operat-
ing position
Air pressure switch time out
–
The air pressure switch is soldered in an operating posi-
tion
Loc 6
Fault with the actuator
–
Actuator defective or blocked
–
Faulty connection
–
Incorrect adjustment
Loc 7
Flame loss
–
Too many flame losses during operation (limitation of
repetitions)
–
Fuel valves dirty or defective
–
Flame detector dirty or defective
–
Burner adjustment incorrect
Loc 8
---
Free
Loc 9
---
Free
Loc 10
Non attributable error (application), internal error
Wiring error or internal error, outlet contacts, other faults
Loc 12
Valve test
Fuel valve 1, leak
Loc 13
Valve test
Fuel valve 2, leak
Loc 14
POC error
POC error valve closure control
Loc 20
Min gas pressure switch open
No gas
Loc 22
Safety loop open
–
Max gas pressure switch open
–
Limit thermostat safety lockout
Loc 60
Analogue power supply source 4...20 mA, I < 4 mA
Wire broken
Loc: 83
PWM fan faulty
–
The PWM fan does not reach the expected speed within
the pre-set period of time, or
–
After reaching the expected speed, the PWM fan once
again falls outside the tolerance range (P650) for a peri-
od of time greater than the time admissible for speed de-
viation (P660)
Loc 138
Reset process successful
Reset process successful
Loc 139
No program module detected
No program module identified
Loc 167
Manual lockout
Manual lockout
Loc: 206
AZL2... incompatible
Use the latest version
Loc: 225
PWM fan faulty
–
The fan speed dropped below the PWM pre-purging
maximum (P675.00) after reaching the pre-purging
speed, or
–
After reaching the ignition load speed, the PWM maxi-
mum ignition load (P675.01) was exceeded
Loc: 226
PWM fan faulty
Configuration error:
–
Low flame speed > high flame speed, or
–
Low flame = 0 rpm, or
–
Maximum speed = 0 rpm
Loc: 227
PWM fan faulty
One or more parameters violate the minimum/maximum limit
rSt Er1
Programme module compatibility fault with the base unit dur-
ing the reset process
The sequence of the program module is not compatible with
the base unit
rSt Er2
Programme module compatibility fault with the base unit dur-
ing the reset process
The hardware of the base unit is not compatible with the pro-
gram module
rSt Er3
Error during the reset process
–
Fault with the program module
–
Program module removed during the reset process