![Riello RS 25/M C05 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/riello/rs-25-m-c05/rs-25-m-c05_installation-use-and-maintenance-instructions_1459842016.webp)
20159324
14
GB
Technical description of the burner
4.12 Servomotor SQN..
Important notes
All interventions (assembly and installation operations,
assistance, etc.) must be carried out by qualified personnel.
Falls and collisions can negatively affect the safety
functions. In this case, the servomotor must not be
operated, even if it displays no evident damage.
Fully disconnect the burner from the mains when working
near terminals and servomotor connections.
Condensation and exposure to water are not allowed.
For safety reasons, the servomotor must be checked after
long periods of non-use.
Technical data
ATTENTION
To avoid accidents, material or environmental
damage, observe the following instructions!
Avoid opening, modifying or forcing the
servomotor.
Mains voltage
220 V -15% +10% ... 240 V + 10%
Mains frequency
50 / 60 Hz +/- 6%
Power absorption
8 VA
Motor
Synchronous
Drive angle
Varying between 0° and 90°
Protection level
IP XX
Cable connection
terminal board for 0.5mm
2
(min.)
and 2.5mm
2
(max.)
Rotation direction
Anticlockwise
Rated torque (max.)
2 Nm
Holding torque
1 Nm
Operation time
24 s. at 90°
Weight approx.
550
kg
Environmental conditions:
Operation
Transport and storage
-20....+60° C
-20...+60°C