20068118
22
GB
Installation
5.4
Operating position
5.5
Preparing the boiler
5.5.1
Introduction
The burners are suitable for working on both flame inversion boil-
ers
(in this case the long head model is recommended) and boil-
ers with a combustion chamber with bottom runoff (three flue gas
circulations), from which the best results of low NO
x
emissions
are obtained.
The maximum thickness of the front hatch of the boiler, complete
with refractory, must not exceed the dimension indicated in
Fig. 13.
5.5.2
Boring the boiler plate
Drill holes in the plate shutting off the combustion chamber, as
illustrated in Fig. 14. The position of the threaded holes can be
marked using the thermal insulation screen supplied with the
burner.
5.5.3
Blast tube length
The length of the blast tube must be selected according to the in-
dications provided by the manufacturer of the boiler, and in any
case it must be greater than the thickness of the boiler door com-
plete with its refractory.
The lengths L available are:
For boilers with front flue passes 13)(Fig. 17), a protection in re-
fractory material 11) must be inserted between the boiler refrac-
tory 12) and the blast tube 10).
This protection must not compromise the extraction of the blast
tube.
For boilers with a water-cooled frontal, a refractory cover is not
necessary 11)-12)(Fig. 17), unless expressly requested by the
boiler manufacturer.
Tab. J
WARNING
The burner is designed to operate only in
positions
1
,
2
,
3
and
4
Installation
1
is preferable, as it is the only
one that allows the maintenance operations
as described in this manual.
Installations
2
,
3
and
4
permit operation but
make maintenance and inspection of the
combustion head more difficult.
DANGER
Any other position could compromise the cor-
rect operation of the appliance.
Installation
5
is prohibited for safety reasons.
2
3
4
5
1
Fig. 12
D3928
Blast tube
Short (mm)
Long (mm)
RS 25-35/E BLU
230
365
mm
A
B
C
RS 25/E BLU
160
224
M 8
RS 35/E BLU
160
224
M 8
Fig. 13
200 mm
D1079
Fig. 14
D455
Содержание RS 25/E BLU Series
Страница 2: ...Translation of the original instructions...
Страница 65: ...63 20068118 GB Appendix Electrical panel layout RS 25 E BLU...
Страница 66: ...20068118 64 GB Appendix Electrical panel layout RS 35 E BLU...
Страница 67: ...65 20068118 GB Appendix Electrical panel layout RS 35 E BLU 3Ph...
Страница 68: ...20068118 66 GB Appendix Electrical panel layout RS 25 35 E BLU...
Страница 69: ...67 20068118 GB Appendix Electrical panel layout RS 35 E BLU 3Ph...
Страница 70: ...20068118 68 GB Appendix Electrical panel layout...
Страница 71: ...69 20068118 GB Appendix Electrical panel layout...
Страница 72: ...20068118 70 GB Appendix Electrical panel layout...
Страница 73: ...71 20068118 GB Appendix Electrical panel layout...
Страница 75: ......