20068118
10
GB
Technical description of the burner
4.6
Maximum dimensions
The dimensions of the burner are shown in Fig. 1.
Bear in mind that inspection of the combustion head requires the
burner to be opened and the rear part drawn back on the guides.
The dimensions of the open burner are indicated by position O.
Tab. E
(1) Blast tube: short-long
4.7
Firing rates
The
maximum output
is chosen within area A.
The
minimum output
must not be lower than the minimum limit
of the diagram:
RS 25/E BLU = 45 kW
RS 35/E BLU = 72 kW
Fig. 1
D3831
mm
A
D
E
F
(1)
H
I
L
O
N
V
M
RS 25/E BLU
442
422
508
230-365
140
305
138
780
84
177
1”1/2
RS 35/E BLU
442
422
508
230-365
152
305
138
780
84
177
1”1/2
WARNING
The firing rate (Fig. 2) was obtained considering a
room temperature of 20°C and an atmospheric
pressure of 1013 mbar (approx. 0 m above sea
level), with the combustion head adjusted as
shown at page 24.
Fig. 2
S8860
Thermal power
Thermal power
C
o
mbustion chamb
e
r
pres
sure
-
mb
a
r
Co
mb
u
s
tion cha
m
ber
pres
sure -
mba
r
RS 25/E BLU
RS 35/E BLU
Содержание RS 25/E BLU Series
Страница 2: ...Translation of the original instructions...
Страница 65: ...63 20068118 GB Appendix Electrical panel layout RS 25 E BLU...
Страница 66: ...20068118 64 GB Appendix Electrical panel layout RS 35 E BLU...
Страница 67: ...65 20068118 GB Appendix Electrical panel layout RS 35 E BLU 3Ph...
Страница 68: ...20068118 66 GB Appendix Electrical panel layout RS 25 35 E BLU...
Страница 69: ...67 20068118 GB Appendix Electrical panel layout RS 35 E BLU 3Ph...
Страница 70: ...20068118 68 GB Appendix Electrical panel layout...
Страница 71: ...69 20068118 GB Appendix Electrical panel layout...
Страница 72: ...20068118 70 GB Appendix Electrical panel layout...
Страница 73: ...71 20068118 GB Appendix Electrical panel layout...
Страница 75: ......