Maintenance
6.1
Notes on safety for the maintenance
The periodic maintenance is essential for the good operation,
safety, yield and duration of the burner.
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time.
Before carrying out any maintenance, cleaning or checking oper-
ations:
6.2
Maintenance programme
6.2.1
Maintenance frequency
6.2.2
Checking and cleaning
Combustion
The optimum calibration of the burner requires an analysis of the
flue gases. Significant differences with respect to the previous
measurements indicate the points where more care should be ex-
ercised during maintenance.
Combustion head
Open the burner and make sure that all the components of the
combustion head are undamaged, not deformed due to high
temperature, free of ambient dirt or dust, free of rusted materials
and adequately positioned.
Make sure that the gas outlet holes for the start-up, on the com-
bustion head distributor, are free of dirt or rust deposits. If in
doubt, disassemble the elbow (Fig. 39 on page 36).
Fan
Check to make sure that no dust has accumulated inside the fan
or on its blades, as this condition will cause a reduction in the air
flow rate and provoke polluting combustion.
Burner
Clean the outside of the burner.
Gas leaks
Make sure that there are no gas leaks on the pipes between the
gas meter and the burner.
UV cell
(Fig. 37)
Minimum value for correct operation: 70 µA. If the value is lower,
it could be due to:
–
exhausted photocell
–
low voltage (lower than 187 V)
–
bad regulation of the burner
In order to measure the current, use a microammeter of 100 µA
c.c., connected in series to the photocell, as in the scheme, with
a capacitor of 100 µF - 1V c.c. at the same level of the instrument.
Gas filter
Replace the gas filter when it is dirty.
Flame inspection window
Clean the glass of the flame inspection window.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics intact,
especially the flue gas temperature and combustion chamber
pressure.
6
Maintenance
DANGER
The maintenance interventions and the calibration
of the burner must only be carried out by qualified,
authorised personnel, in accordance with the con-
tents of this manual and in compliance with the
standards and regulations of current laws.
DANGER
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
Wait for the components in contact with heat
sources to cool down completely.
The gas combustion system should be checked at
least once a year by a representative of the man-
ufacturer or another specialised technician.
The operator must use the required equipment
during maintenance.
Fig. 37
D1143
Содержание RS 200/EV BLU TL
Страница 2: ...Original instructions...
Страница 42: ...20080730 40 GB Appendix Electrical panel layout 0 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2 67 8 9...
Страница 43: ...41 20080730 GB Appendix Electrical panel layout 0 1 1 0 2 0 00 0 1 3 414 56 2 7 8 03 59 3 A...
Страница 44: ...20080730 42 GB Appendix Electrical panel layout...
Страница 45: ...43 20080730 GB Appendix Electrical panel layout 0 1 1 2 1 1 1 1 1 3 3 3 1 1 0 1 1 4 4 1 4 41 1 1 5 6 4 4 768 9...
Страница 49: ......
Страница 50: ......
Страница 51: ......