Faults - Possible causes - Solutions
(1)
The control box is fitted with a disc rotates during the firing programme, which can been seen through the transparent lock-out
reset button.
When the burner does not fire or comes to a half following a fault, the symbol which appears behind the reset button indicates the
type of problem.
Pump unprimes after pro-
longed pause
Return pipe not immersed in fuel
Bring to same height as suction
pipe
Air enters suction piping
Tighten connectors
Pump leaks gas oil
Leakage from sealing organ
Replace
pump
Dirty combustion head
Nozzle or filter dirty
Replace
Unsuitable nozzle delivery or angle
See recommended nozzles
Loose nozzle
Tighten
Impurities on flame stability disk
Clean
Erroneous head adjustment or not enough air
Adjust, open air damper
Blast tube length unsuited to boiler
Contact boiler manufacturer
During operation, the burner
stops in lock out
Dirty or defective photocell
Clean or replace
Defective air pressure switch
Replace