9
20034293
GB
Technical description of the burner
4.3
Countries of destination - Burner categories
Tab. B
4.4
Technical data
Tab. C
(1)
Reference conditions: ambient temperature 20°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure at test point 4)(Fig. 6 at page 13) with zero pressure in the combustion chamber and maximum burner output.
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated
output.
Country of destination
Gas category
IT - AT - GR - DK - FI - SE - EE - CZ - HU - LT - SK - BG - LV - SI - PL
II2H3B/P
ES - GB - IE - PT
II2H3P
NL
II2L3B/P
FR
II2Er3P
DE
II2ELL3B/P
BE
I2E(R)B, I3P
LU
II2E3B/P
NO - CY - MT
I3B/P
RO
I2H
Model
RLS 250/M MZ
Type
1302 T
Output
(1)
Delivery
(1)
2
nd
stage
kW
kg/h
1230 - 2460
104 - 207
min. 1
st
stage
kW
kg/h
550
47.5
Fuel
Gas oil, viscosity at 20 °C: 6 mm
2
/s max (1,5 °E - 6 cSt)
Gas oil and Blends of gas oil and bio fuel (FAME in accordance with EN 14214)
up to 10%
Natural gas: G20 (methane) - G21 - G22 - G23 - G25
Gas pressure at maximum delivery
(2)
Gas: G20/G25
mbar
42.9/55.7
Operation
- Intermittent (min. 1 stop in 24 hours)
- Gas oil: two-stage (high and low flame) and single-stage (all - nothing)
- Gas: Progressive two-stage or modulating by kit (see Appendix - Accessoires)
Nozzles
number
2
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperatur
°C
0 - 40
Combustion air temperature
°C max
60
Pump
delivery (at 12 bar)
pressure range
fuel temperatur
kg/h
bar
° C max
230
10 - 21
90
Noise levels
(3)
dB(A)
85
Содержание RLS 250/M
Страница 2: ...Original instructions ...
Страница 45: ...43 20034293 GB Appendix Electrical panel layout ...
Страница 46: ...20034293 44 GB Appendix Electrical panel layout ...
Страница 47: ...45 20034293 GB Appendix Electrical panel layout ...
Страница 48: ...20034293 46 GB Appendix Electrical panel layout ...
Страница 49: ...47 20034293 GB Appendix Electrical panel layout ...
Страница 51: ......