Technical description of the burner
4.8
Firing rates
The burners RLS 70 - 100 - 130 can work in two ways: one-stage
or two-stage.
The
MAXIMUM OUTPUT
is chosen within area A (and B for RLS
130)(Fig. 2). To use also area B (RLS 130), the combustion head
has to be pre-calibrated. See "Combustion head pre-calibration”
on page 19
The
MINIMUM OUTPUT
must not be lower than the minimum
limit of the diagram:
RLS 70 = 232 kW = 19.0 kg/h
RLS 100 = 349 kW = 29.5 kg/h
RLS 130 = 465 KW = 39.0 kg/h
ATTENTION
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
shown on page 21.
Pressure in the cham
ber
pressure -
mba
r
Thermal power -
kW
Fig. 2
RLS 70
D1194
Pressure in the chamb
er
pressure -
mbar
Thermal power -
kW
RLS 100
Pressure in the chambe
r
pressure -
mbar
Thermal power -
kW
RLS 130
Содержание RLS 100
Страница 2: ...Translation of the original instructions ...
Страница 55: ...53 20148653 GB Appendix Electrical panel layout 0 1 2 1 2 3 3 3 4 3 5 3 3 3 3 3 3 3 63 6 6 3 3 4 3 ...
Страница 56: ...20148653 54 GB Appendix Electrical panel layout 0 1 1 1 ...
Страница 57: ...55 20148653 GB Appendix Electrical panel layout 0 1 1 1 2 2 ...
Страница 58: ...20148653 56 GB Appendix Electrical panel layout 0 1 2 1 3 3 0 4 0 3 5 6 7 6 7 8 99 8 99 6 7 4 2 1 8 6 6 RLS 70 ...
Страница 60: ...20148653 58 GB Appendix Electrical panel layout 0 1 2 1 3 3 0 4 0 3 5 6 7 6 7 8 99 8 99 6 7 4 2 1 6 6 RLS 130 ...
Страница 62: ......
Страница 63: ......