background image

2374

6

 

PRESSURE:  

12  bar: 

pressure suitable for light oil in most cases.

14  bar: 

improves flame retention; it is therefore suitable for ignitions at low temperatures.

FOR KEROSENE DECREASE PRESSURE

8 bar: 

pressure suitable for kerosene in most cases.

10 bar: 

maximum pressure for kerosene.

 

COMBUSTION HEAD SETTING

This is done when fitting the nozzle, with the blast tube removed.
It depends on the output of the burner and is carried out by rotating the regulating rod, till the terminal
plane of the blast tube is level with the set-point, as indicated in the schedule. 

 

AIR DAMPER ADJUSTMENT 

The regulation  of  the air-rate is made by adjusting the air
damper (1), after loosing the screws (2). 
The settings indicated in the schedule refer to the burner
with its metal cover fitted and the combustion chamber
with “zero” depression.
These regulations are purely indicative. Each installation
however, has its own unpredictable working conditions: actu-
al nozzle output; positive or negative pressure in the
combustion-chamber, the need of excess air, etc. All these
conditions may require a different air-damper setting.

It is important to take account of the fact that the air
output of the fan differs according to whether the
burner has its metal cover fitted or not.  
Therefore we recommended to proceed as follows:

–  adjust the air damper as indicated in the schedule (4);
–  mount the cover, simply by means of the upper screw;
– check smoke number;
–  should it become necessary to modify the air output, remove the cover by loosening the screw,

adjust the air damper, remount the cover and finally recheck the smoke number.

2

3

Blast tube

Regulating rod

Shutter

Terminal plane of the blast tube

D5244

2

1

3

5

In the sketch on the left, the combustion
head is set for an output of  1.00 GPH at
12 bar 

(for gas-oil)

 or 1.25 GPH at 8 bar

(for kerosene). 

The shutter is level with set-point  

3

, as

required by the schedule at page 5

2

1

D5514

2

4

Содержание R40 G7 140-160

Страница 1: ...Installation use and maintenance instructions 2902374 5 06 2015 Light oil and kerosene burners One stage operation CODE MODEL TYPE 3745959 R40 G7 140 160 459T55 3745961 R40 G7 160 200 459T55 GB...

Страница 2: ......

Страница 3: ...Single phase 230V 10 50Hz Motor Run current 0 85A 2850 rpm 298 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Maximum pressure 14 bar 203 psi Absorbed electrical power 0 16 kW 1 Re...

Страница 4: ...11 204 D5235 189 83 83 170 4 5 It is necessary that the insulating gasket 7 fig 1 is placed between the boiler door and the burner flange This insulating gasket has six holes which if necessary can be...

Страница 5: ...flexible pipes conditions Using kerosene they have to be replaced at least every 2 years O A metal bowl filter with replaceable micronic filter must be fitted in the oil supply pipe PRIMING THE PUMP...

Страница 6: ...arrow The photoresistance is fitted directly into the control box underneath the ignition trans former on a plug in support TESTING Check the shut down of the burner by opening the thermostats CARRIE...

Страница 7: ...on chamber FUEL LIGHT OIL FUEL KEROSENE NOZZLES RECOMMENDED Monarch type R NS Delavan type W A E Steinen type Q H Danfoss type S B H Nozzle Pump pressure Burner output Comb head adjustment Air damper...

Страница 8: ...ative Each installation however has its own unpredictable working conditions actu al nozzle output positive or negative pressure in the combustion chamber the need of excess air etc All these conditio...

Страница 9: ...et point further ahead than indicated in the instructions Example the instructions require to set the combustion head on set point 3 Instead the setting is made on set point 4 4 FAN AIR DAMPER ADJUSTM...

Страница 10: ......

Страница 11: ......

Страница 12: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Отзывы: