ELECTRODE SETTING

BURNER START-UP CYCLE

ONLY FOR LIGHT OIL

ADJUSTMENTS, TO AVOID FLAME - DETACHMENT, AT BURNER - IGNITION

This inconvenience can occur, when the temperature of the gas-oil decreases below +8 °C.

1)  CORRECT POSITIONING OF THE ELECTRODES (see figure above)

2)  PUMP - SETTING

When the temperature of the gas-oil decreases below + 8 °C, increase the pressure to 14 bar.

3) COMBUSTION-HEAD SETTING

Regulate the combustion-head one set-point further ahead than indicated in the instructions.

Example:

 

the instructions require to set the combustion-head on set-point  3.
Instead, the setting is made on set-point 4.

4)  FAN - AIR DAMPER ADJUSTMENT

Adjust the damper, reducing the excess air until the Bacharach number is not near 1.
(i.e.  a combustion with the lowest possible excess-air).

Attention:

Before removing or assembling the
nozzle, loosen the screw 

(A)

 and

move the electrodes ahead.

2 – 2.3

 mm

4

± 

0.3 mm

IMPORTANT:
THESE  DIMENSIONS
MUST BE OBSERVED

D5230

A

Normal

Lock-out, due to light-failure

Thermostat

Motor

Ignition transformer

Valve

Flame

Lock-out lamp

~

 

12s

D5229

~

 

12s

~

 

5s

Содержание R40 G7 140-160

Страница 1: ...Installation use and maintenance instructions 2902374 5 06 2015 Light oil and kerosene burners One stage operation CODE MODEL TYPE 3745959 R40 G7 140 160 459T55 3745961 R40 G7 160 200 459T55 GB...

Страница 2: ......

Страница 3: ...Single phase 230V 10 50Hz Motor Run current 0 85A 2850 rpm 298 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Maximum pressure 14 bar 203 psi Absorbed electrical power 0 16 kW 1 Re...

Страница 4: ...11 204 D5235 189 83 83 170 4 5 It is necessary that the insulating gasket 7 fig 1 is placed between the boiler door and the burner flange This insulating gasket has six holes which if necessary can be...

Страница 5: ...flexible pipes conditions Using kerosene they have to be replaced at least every 2 years O A metal bowl filter with replaceable micronic filter must be fitted in the oil supply pipe PRIMING THE PUMP...

Страница 6: ...arrow The photoresistance is fitted directly into the control box underneath the ignition trans former on a plug in support TESTING Check the shut down of the burner by opening the thermostats CARRIE...

Страница 7: ...on chamber FUEL LIGHT OIL FUEL KEROSENE NOZZLES RECOMMENDED Monarch type R NS Delavan type W A E Steinen type Q H Danfoss type S B H Nozzle Pump pressure Burner output Comb head adjustment Air damper...

Страница 8: ...ative Each installation however has its own unpredictable working conditions actu al nozzle output positive or negative pressure in the combustion chamber the need of excess air etc All these conditio...

Страница 9: ...et point further ahead than indicated in the instructions Example the instructions require to set the combustion head on set point 3 Instead the setting is made on set point 4 4 FAN AIR DAMPER ADJUSTM...

Страница 10: ......

Страница 11: ......

Страница 12: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Отзывы: