COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment
and testing must be carried out observing the instruction manual of the boiler, including verification of
the CO and CO

2

 concentration in the flue gases, their temperatures and the average temperature of

the water in the boiler.
To suit the required appliance output, fit the nozzle then adjust the pump pressure, the setting of the
combustion head and the air damper opening in accordance with the following schedule. The values
in the table refer to 12.5% CO

2

 at sea level and to “zero” pressure in the combustion chamber.

FUEL LIGHT OIL 

FUEL KEROSENE 

 

NOZZLES RECOMMENDED:

 Monarch  type R - NS;

Delavan  type W - A - E

Steinen  type Q - H ;

Danfoss  type S - B - H

Nozzle

Pump pressure

Burner output

Comb. head 

adjustment

Air damper

adjustment

GPH

Angle

bar

kg/h ± 4%

Set-point

Set-point

0.60

60° / 80°

12

2.50

1

1.2

0.65

60° / 80°

12

2.80

1.5

1.4

0.75

60°

12

3.10

2

1.8

0.85

60°

12

3.60

2.5

2.2

1.00

60°

12

4.29

3

2.6

1.10

60°

12

4.72

4

3

1.25

60°

12

5.30

5

3.5

1.35

60°

12

5.80

6

4.2

     Angle: 60°

in most cases.

80°

in case of flame detachment, during ignitions at low temperatures.

Nozzle

Pump pressure

Burner output

Comb. head 

adjustment

Air damper

adjustment

GPH

Angle

bar

kg/h ± 4%

Set-point

Set-point

0.85

60°

8

2.51

1

1.2

1.00

60°

8

2.95

1.5

1.4

1.10

60°

8

3.25

2

1.8

1.25

60°

8

3.69

3

2.2

1.35

60°

8

3.99

3.5

2.4

1.50

60°

8

4.43

4.5

2.7

1.75

60°

8

5.20

6

3.2

2.00

60°

8

5.80

6

4.2

1

2

3

4

1

2

3

4

1

Содержание R40 G7 140-160

Страница 1: ...Installation use and maintenance instructions 2902374 5 06 2015 Light oil and kerosene burners One stage operation CODE MODEL TYPE 3745959 R40 G7 140 160 459T55 3745961 R40 G7 160 200 459T55 GB...

Страница 2: ......

Страница 3: ...Single phase 230V 10 50Hz Motor Run current 0 85A 2850 rpm 298 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Maximum pressure 14 bar 203 psi Absorbed electrical power 0 16 kW 1 Re...

Страница 4: ...11 204 D5235 189 83 83 170 4 5 It is necessary that the insulating gasket 7 fig 1 is placed between the boiler door and the burner flange This insulating gasket has six holes which if necessary can be...

Страница 5: ...flexible pipes conditions Using kerosene they have to be replaced at least every 2 years O A metal bowl filter with replaceable micronic filter must be fitted in the oil supply pipe PRIMING THE PUMP...

Страница 6: ...arrow The photoresistance is fitted directly into the control box underneath the ignition trans former on a plug in support TESTING Check the shut down of the burner by opening the thermostats CARRIE...

Страница 7: ...on chamber FUEL LIGHT OIL FUEL KEROSENE NOZZLES RECOMMENDED Monarch type R NS Delavan type W A E Steinen type Q H Danfoss type S B H Nozzle Pump pressure Burner output Comb head adjustment Air damper...

Страница 8: ...ative Each installation however has its own unpredictable working conditions actu al nozzle output positive or negative pressure in the combustion chamber the need of excess air etc All these conditio...

Страница 9: ...et point further ahead than indicated in the instructions Example the instructions require to set the combustion head on set point 3 Instead the setting is made on set point 4 4 FAN AIR DAMPER ADJUSTM...

Страница 10: ......

Страница 11: ......

Страница 12: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Отзывы: