Email logic menu
/------------------------/
/ Email logic /
/------------------------/
Email 1 Email 2 Email 3 Logic:
UPS Lock.......:
X<-- 0 0
And
Ovrload/Ovrtemp:
X 0 0
And
UPS Failure....:
X 0 0
And
On bypass......:
X 0 0
And
Battery work...:
X 0 0
And
Battery low....:
X 0 0
And
Communic lost..:
X 0 0
And
With this menu it can be established to which addresses the e-mails will be sent when certain
events occurs. One or more addresses can be associated with each event and in the latter case,
when the event occurs, notification e-mails will be sent to all the addresses associated with it.
U
se the ENTER key to change the selected configuration (“X” or “0”).
X: when the event occurs,
NetMan plus
sends a notification e-mail to the corresponding
addresses (see “
Email logic
menu” to set the addresses);
0: when the event occurs,
NetMan plus
does not send a notification e-mail to the
corresponding addresses;
The following table describes the meaning of the events. These can vary depending on the UPS
connected.
Event
Meaning
UPS Lock
UPS is locked
Ovrload/Ovrtemp
UPS in overload or in overtemperature
UPS Failure
Failure of the UPS
On bypass
Operation from bypass
Battery work
Operation from battery
Battery low
Battery low
Communic lost
Communication between the UPS and the device has been interrupted
SENTR level 2
Presence of an internal UPS failure (this condition emulates the level
of modem alarm for UPSs of the SENTR type)
SENTR level 3
Presence of a failure in the UPS, excluding those envisaged in the
previous point (this condition emulates the level of modem alarm for
UPSs of the SENTR type)