65
Parameter
Description
10 CLI
Thermoregulation curve with external
probe connected to the boiler or external
web probe via the APP (available with OT-
Bus connection between the WiFi Box and
the boiler or the RF receiver and the boiler
or the
Hi, Comfort T100
and the boiler, if
provided for by the OTBus protocol).
Default set to 1.2°C.
The value can be set from 0.2°C to 3°C.
The parameter in question affects the cal-
culation of the heating delivery setpoint
temperature.
ESC
MODE
100
80
60
40
20
20
16
12
8
4
0
3
2,5
2
1,5
1,2
1
0,8
0,6
0,4
0,2
-4
-8 -12 -16
T Mand risc = T Mand Curva + ( CLI * InFL *
Δ
T Amb)
T Mand Curva
= Delivery temperature calculated using the thermoregu-
lation curve set under parameter CLI
CLI
= thermoregulation curve
InFL
= room influence
Δ
T Amb
= (room temperature set) – (current room temperature)