8
INSTALLATION
4
INSTALLATION
9
Condexa Pro3 IN-EXT
heating units must be installed in
conformity to the latest provisions of the law and standards
in force concerning heating units, condensing boilers and/
or other applicable regulatory provisions.
4.1
Product packaging and identification
The
Condexa Pro3 IN-EXT
heating unit is supplied, packed and
protected by a strapped carton.
Figure 5
1
Boiler
2
Control panel
3
EC marking/Symbol cartouche
4
Packaging
5
Polyester corners
6
Polyester protection panel
7
Strap
Details of the product are written on the outside: model, power,
version and type of fuel. Contact your local dealer in case of any
differences with the order.
Ensure the goods are intact and complete after unpacking them.
9
Do not leave the packaging within the reach of children as it
could be a potential source of danger.
The tag on the front side of the boiler’s electrical board, contains
the following information:
− Product name
− Serial number
− Product identification code
− CE certification number
− Gas type and pressures from mains
− Power type from mains
− Rated heat capacity (Qn)
− Rated working power (Pn)
− Efficiency according to 92/42/EEC Directive
(η)
− Max pressure and temperature (Pms)
− Primary system (T)
− NOx class (NOx)
Figure 6
0
It is forbidden to remove or mishandle the identification
plates, markings and any other making it difficult to safely
identify the product.
4.2
Installation premises
The heating unit must be installed in premises used exclusively
for the latter conforming to standards and legislation in force
and where combustion exhaust products and combustion air
intake is conveyed out of said premises. Where combustion air is
instead taken from the installation premises then the latter must
be equipped with suitably sized vents conforming to standards.
9
The space required to reach the safety and adjustment de-
vices and to carry out maintenance must be considered. We
recommend leaving a space of at least 500 mm at the back
of the appliance.
9
Ensure that the degree of the heating unit’s electrical pro-
tection is compatible with the characteristics of the instal-
lation premises.
9
Electrical parts must be placed at a height of no less than
500 mm from the ground where heating units are supplied
with fuel gas with specific weight exceeding that of air.
9
Heating units may not be installed out in the open (unless
they are not specific outdoor units).
9
The heating unit is equipped with a frost protection func-
tion, useful for installations where the temperature of the
environment could be below 0°C. Gas and electricity must
be supplied for this system to work, apart from a correctly
pressurized water circulation system and the system must
not be in shutdown due to any type of error.
Содержание Condexa Pro3 230 IN V02
Страница 1: ...cod 20060249 rev 10 12 2015 Condexa Pro3 230 345 460 IN EXT EN INSTALLATION INSTRUCTIONS...
Страница 36: ...36 WIRING DIAGRAMS 12 WIRING DIAGRAMS...
Страница 37: ...37 WIRING DIAGRAMS Valvola 2 vie Circolatore...
Страница 42: ...42 WATER IN CENTRAL HEATING SYSTEMS...
Страница 43: ...43 WATER IN CENTRAL HEATING SYSTEMS...