24
USE AND ADJUSTMENT
8.7
Test mode
In test mode it is possible to generate a high temperature heating demand at maximum power and at minimum power.
All system fans must be activated. If the installer turns off the switch for some Slaves, the others, connected to the Master, must
continue to operate.
Proceed as follows to enter Test mode from Display mode:
POS.
VISUALIZED VALUES
DISPLAY
1
Press
“Set/esc”
and at the same time for 5 s.
After 5 s select the maximum speed or the minimum speed with the and buttons.
All system fans will operate at the selected speed.
The first digit indicates the selected speed (H = maximum speed; L = minimum speed).
The other two digits display the delivery temperature. E.g: T1 = 80°C.
2
Press
“OK”
to exit Test mode and return to Display mode.
8.8
Error mode
The display starts to flash in case of a fault originating from any heating element.
Follow the procedure indicated for identifying the errors.
POS.
PROCEDURE
DISPLAY
1
The display starts to flash to indicate one or more errors.
1.b
Press : the address of the first unit will appear on the display, alternating with the first error code.
Press again to display the rest of the errors for this unit.
The errors of the subsequent units that are not functioning will be displayed in succession, pressing
the button. By pressing the button, the errors will be displayed in reverse order (E.g. unit 2 error
code E05). If the errors originate from the Master card, they are displayed as unit 00 errors (U 00 +
error code).
2
Press
“Set/esc”
to exit Error mode and return to Display mode.
See the chapter "Fault list" for a complete list of the errors.
8.9
Permanent block
In the case of burners with a permanent block, the
“Reset”
button must be pressed to reset their operation.
If the
“Reset”
button is pressed while in Display mode, all the Slave heating elements will be reset.
If the
“Reset”
button is pressed while displaying the error that caused the permanent block, only the heating element related to
the block will be reset.
Содержание Condexa Pro3 230 IN V02
Страница 1: ...cod 20060249 rev 10 12 2015 Condexa Pro3 230 345 460 IN EXT EN INSTALLATION INSTRUCTIONS...
Страница 36: ...36 WIRING DIAGRAMS 12 WIRING DIAGRAMS...
Страница 37: ...37 WIRING DIAGRAMS Valvola 2 vie Circolatore...
Страница 42: ...42 WATER IN CENTRAL HEATING SYSTEMS...
Страница 43: ...43 WATER IN CENTRAL HEATING SYSTEMS...