Function 

Parameter Description 

Value range 

Default 

value

 Set 

value

 

Min 

Max 

External heat source 

air temperature limit

148

This code is used to set the outside air temperature threshold value below which only 

the external heat source will be operative as per algorithm. (Heat Pump Stop)

-20°C 65°C

-20°C

Temperature list

149

Code used to set which temperature the control panel should display in the temperature 

zone.

1. Indoor air temperature

2. Outlet water temperature (from LWT sensor)

3. N.A.

4. Refrigerant temperature (from TR sensor)

5. Suction temperature (from TS sensor)

6. Discharge temperature (from TD sensor)

7. Refrigerant temperature (from TE sensor)

1

7

1

Auxiliary outdoor air 

temperature limit

150

This code is used to set the outside air temperature threshold value below which both 

the heat pump and the external heat source will be operative as per algorithm.

-20°C 30°C

0°C

Auxiliary delay

151

This code is used to set the delay time after which, when (temperature set in code 148) 

< Outside Air Temperature < (temperature set in code 150), the external heat source 

will switch on.

The counting of the time starts when the activation of the external heat source is 

required as per algorithm.

1 Min 60 Min

10 Min

Auxiliary hysteresis

152

This code is used to set the hysteresis temperature needed to activate the external 

heat source.

1°C

20°C

5°C

Domestic hot water in 

off mode

153

Code to establish whether, when the system is in off mode, the domestic hot water 

production logic can be activated:

1. Yes, the domestic hot water logic is always active

2. No, the domestic hot water logic can be activated only in Heating or Cooling mode

1

2

1

Status of external 

heat source

154

Code used to establish the status of the external heat source when this later is activated 

and the outside air temperature is below the temperature value set with parameter 148:

0. Always active

1. On/Off depending by actual room temperature vs room temperature set-point (same 

hysteresis of the thermostat function). If the command is not installed or the room 

sensor is unavailable, On/Off depends on the water set-point (+1/-4 °C of hysteresis)

2. On/Off depending on the water set-point (+1/-4 °C of hysteresis).

0

2

1

Main water pump vs 

external heat source 

status

155

This code is used to define the water pump logic when the external heat source is 

activated and the outside air temperature < temperature value set in Code 148

0. Always off

1. On/Off depending on the On/Off status of the external heat source

2. Always on

0

2

1

Electric trace heater/

additional water pump

156

Code used to select the output connected to PIN 12 on the terminal board. In case an 

additional water pump option is active, this code is used to select its operating system with 

respect to the domestic hot water request (ACS) (if outside air temperature > (temperature 

value set with Code 148).

0. Electric heat tracing installed for the antifreeze system

1. Additional water pump On/Off depending on the main water pump logic. This means that if the 

DHW is on, the additional water pump is ON.

2. Additional water pump On/Off depending on the main water pump logic, but always OFF when 

the DHW is on.

0

2

1

Additional water 

pump

157

This code is used to establish the additional water pump, if it has been installed, when 

the outside air temperature < temperature value set with Code 148:

0. Always off

1. On/Off depending on the On/Off status of the external heat source

2. Always on

0

2

2

Delta air set point

158

Code used to establish the hysteresis with respect to the ambient temperature set point 

to switch off the unit when control panel system is installed and used as a thermostat 

(100 control panel code = 4).

0.2°C

1°C

0.3 °C

Function 

Parameter Description 

Value range 

Default 

value

 Set 

value

 

Min 

Max 

Unit configuration

302

This code is used to configure the unit:

0. Cooling only

1. Heating and cooling

2. Heating only

0

2

1

Table of factory parameters and functions

  

 
 

 36

Содержание AriaPRO 004 ME

Страница 1: ...Installation Servicing Instructions THESEINSTRUCTIONS TOBERETAINED BYUSER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of...

Страница 2: ...2...

Страница 3: ...maintenance operations please adopt the appropriate attire and accident prevention devices The Manufacturer waives all and any responsibility for failure to observe the safety and accident prevention...

Страница 4: ...onents Micro processor electronic control regulation performance Climate control The AriaPRO range units are designed for the production of refrigerated water for air conditioning heated water for hea...

Страница 5: ...1 58 1 96 3 46 4 42 EER 9 3 02 3 2 98 2 96 2 95 ESEER 9 4 36 4 51 4 15 4 22 4 31 Generalities Sound pressure in heating mode dB A 42 42 44 47 48 Sound pressure in cooling mode dB A 44 44 45 48 49 Com...

Страница 6: ...A Cold zone Low temperature 30 35 C s 133 120 110 115 133 SCOP 3 41 3 07 2 82 2 94 3 40 Pdesign 6 03 7 75 6 46 15 75 17 25 Annual consumption kW h 4 148 5 927 5 381 12 620 11 945 Warm zone Low tempera...

Страница 7: ...hot water production may be limited according to the settings of the safety devices in the equipment For technical activities please refer to the technical tag mounted on board the machine It is forbi...

Страница 8: ...mm 356 640 G mm 466 750 H mm 40 44 L mm 60 69 A Flow rate l s B Available static pressure kPa 0 1 0 0 75 65 B A 4 6 55 45 35 25 15 5 75 65 B 55 45 35 25 15 5 0 2 0 3 0 4 0 5 0 1 0 0 A 0 2 0 3 0 4 0 5...

Страница 9: ...s and defrost OAT Outside air probe LF Frequency Limiting IS Domestic water input SV Three way domestic water valve Y Yellow O Orange R Red G Grey A Brown C Black V Violet B Blue W White Y G Yellow Gr...

Страница 10: ...3 J16 J5 2 J16 4 EHTR WP J5 3 J5 J16 5 J5 4 J16 6 J5 5 21CF 7 6 5 4 3 2 1 J20 7 REMOTE J20 6 1FS 1 2 22CF 1 2 1 J15 1 J20 5 J15 J17 1 J17 2 J10 1 J20 4 J20 1 J10 2 J20 3 J17 J10 3 J20 2 J10 1OAT J10 4...

Страница 11: ...P20 P35 P34 P19 P18 P04 P05 P06 1P C BOARD P11 P08 1MCC1530 3CF 1 2 3 4CF 1 2 3 CN805 1 1 P33 2R P32 5CF 2 1 4CM 2 1 P31 2 10 J4 1 P30 CN701 2 03 J3 1 6CF 1 2 3 1 2 08 J1 1 1RV F7 P03 P10 P02 CN806 1...

Страница 12: ...3 J16 J5 2 J16 4 EHTR WP J5 3 J5 J16 5 J5 4 J16 6 J5 5 21CF 7 6 5 4 3 2 1 J20 7 REMOTE J20 6 1FS 1 2 22CF 1 2 1 J15 1 J20 5 J15 J17 1 J17 2 J10 1 J20 4 J20 1 J10 2 J20 3 J17 J10 3 J20 2 J10 1OAT J10 4...

Страница 13: ...P35 P34 P19 P18 P04 P05 P06 1P C BOARD P11 P08 1MCC1530 42CF 1 2 3 43CF 1 2 3 CN805 1 1 P33 P32 2R 44CF 2 1 9CM 2 1 P31 P30 CN701 45CF 1 2 3 1 1RV F7 P03 1F 1 2 P10 P02 CN806 1 CN300 CN700 CN503 CN502...

Страница 14: ...HUMIDITY J5 1 J16 3 J16 J5 2 J16 4 EHTR WP 12 J5 3 J5 J16 5 J5 4 EHS DFR J16 6 4 J5 5 60CF 7 6 5 4 3 2 1 J20 7 ALARM 5 J20 6 1FS 1 2 61CF 1 2 1 J15 1 J20 5 J15 J17 1 J17 2 16 J10 1 J20 4 J20 1 J10 2 J...

Страница 15: ...2CM 1 2 3 7CF 1 2 3 P12 N P13 R 1 8CF 1 2 9CF 1 2 1 CN05 CN04 3 P21 10CF 1 2 3 1 CN303 P24 1 11CF 1 2 3 4 5 12CF 1 2 3 4 5 1 1FM CN800 CN06 P28 J4 1 2 10 J3 1 2 03 J1 1 2 08 P29 13CF 1 2 3 4 5 ED 1 CN...

Страница 16: ...UMIDITY J5 1 J16 3 J16 J5 2 J16 4 EHTR WP 12 J5 3 J5 J16 5 J5 4 EHS DFR J16 6 4 J5 5 32CF 7 6 5 4 3 2 1 J20 7 ALARM 5 J20 6 1FS 1 2 33CF 1 2 1 J15 1 J20 5 J15 J17 1 J17 2 16 J10 1 J20 4 J20 1 J10 2 J2...

Страница 17: ...00 WHITE CN710 WHITE SW802 SW804 SW803 ON ON ON 4 3 2 1 4 3 2 1 4 3 2 1 SW801 CN704 BLUE SW800 RY704 P04 CN701 WHITE P05 CONTROL P C BOARD MCC1571 P06 CN04 WHITE P07 CN200 F03 T10A 250V F01 T25A 250V...

Страница 18: ...HUMIDITY J5 1 J16 3 J16 J5 2 J16 4 EHTR WP 12 J5 3 J5 J16 5 J5 4 EHS DFR J16 6 4 J5 5 84CF 7 6 5 4 3 2 1 J20 7 ALARM 5 J20 6 1FS 1 2 85CF 1 2 1 J15 1 J20 5 J15 J17 1 J17 2 16 J10 1 J20 4 J20 1 J10 2 J...

Страница 19: ...ortation The unit must be handled by skilled technicians appropriately equipped and with the appropriate tools to manage the unit s weight in compliance with the accident prevention regulations When h...

Страница 20: ...units must Be placed on a level surface able to support their weight Be placed on a sufficiently rigid floor slab that does not transfer vibrations to the rooms below or next door It is suggested to...

Страница 21: ...so that the pipes can be washed without having to disconnect the unit The connection pipes should be of a suitable diameter and suppor ted so that their weight does not rest on the appliance It is ma...

Страница 22: ...e connection points in the pre cut part Remove the pre cut part Remove the hole s cutting edges Insert the supplied cable protections Only for size 015 use the strain relief supplied with the unit Thr...

Страница 23: ...C B D C 004 006 008 D C A E 012 015 Legend A Position 4 Led Inverter diagnostics board 12ME 15ME B LED GMC position Diagnostic board C Installation terminal strip D Cable holder E Strain relief 23...

Страница 24: ...d the connection cable of the control panel through the hole in the base Anchor the base with appropriate screws and bolts Connect the cable to the clamps on the control panel paying attention to pola...

Страница 25: ...charge Operations After deactivating the unit Position the remote switch in the off position Position the system s main switch in the off position Deactivate the indoor terminal units by positioning t...

Страница 26: ...ed flames or high temperature bodies in case of leaks please air the rooms thoroughly Do not charge the refrigerating circuits with a different refrigerant from the prescribed one Do not use oils that...

Страница 27: ...START TIME Activates the programming menu displaying the beginning of the six periods of time scheduled PERIOD Activates the programming menu displaying the six periods of time scheduled DAYS Activate...

Страница 28: ...meter Activate the arrow keys Set the current value Push the OK key to confirm Setting of room temperature Push the mode key Select the desired operation mode Activate the arrow keys Set the desired t...

Страница 29: ...change of the next parameter shall be enabled To move Activate the arrow keys To confirm Push the OK key to confirm Refer to the functions table for further details on the various parameters Quick key...

Страница 30: ...5 10 15 20 15 20 25 30 35 40 45 par 4 1 2 3 4 15 25 35 45 55 65 15 10 5 0 5 10 15 20 25 par 4 1 2 3 4 1 MAX W T W1 Par No 121 2 NO HEAT T W1 Par No 120 3 REGION T O Par No 118 4 STOP H T O Par No 119...

Страница 31: ...s Before resetting it is necessary to remove the cause of the anomaly Abnormal operations are notified by the Control Panel with numeric codes Part of the alarms resets automatically while others requ...

Страница 32: ...etc Discharge temp error Power supply error Heat sink overheat error Gas leak detection 4 way valve reverse error High pressure protective operation Fan system error Driving element short circuit Pos...

Страница 33: ...rature 11 Lock Outdoor Temperature measured by the sensor C 30 C 90 C Outdoor temperature GMC 12 Lock Outdoor temperature read by the GMC board C 20 C 65 C Room sensor temperature adjustment 13 Correc...

Страница 34: ...d for ACS when External Air Temperature tem perature set with code 148 2 Humidity control 1 2 2 Frost Delta set point 109 Code used to set the frost set point delta used by the antifreeze system as pe...

Страница 35: ...3 Heating 4 Faulty 5 Defrost Lock Compressor max frequency 132 The code indicates the maximum frequency of the compressor calculated by the GMC control board Lock Requested frequency 133 The code ind...

Страница 36: ...0 Always active 1 On Off depending by actual room temperature vs room temperature set point same hysteresis of the thermostat function If the command is not installed or the room sensor is unavailabl...

Страница 37: ...s The manufacturer s literature including Benchmark Checklist and Service Record has been explained and left with the customer Yes CENTRAL HEATING MODE Heating Flow Temperature C Heating Return Temper...

Страница 38: ...ature Date Engineer Name Company Name Telephone No Operative ID No Comments Signature Date Engineer Name Company Name Telephone No Operative ID No Comments Signature Date Engineer Name Company Name Te...

Страница 39: ......

Страница 40: ...ra co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the right...

Отзывы: