Pre-set curves
There are six available curves fro heating and two for cooling, accessible
through parameters 112 and 117 in the installer’s configuration table.
The curves are set so as to maintain and indoor temperature of 20°C.
1
Heating
2
Cooling
x
Outdoor temperature
Y
Water temperature
1
2
3
4
5
6
15
20
25
30
35
40
45
50
55
60
65
-15
-10
-5
0
5
10
15
20
25
°C
°C
Fan Coil
x
y
x
y
1
1
15
-20
-15
-10
-5
0
5
10
15
20
25
°C
°C
20
25
30
35
40
45
50
55
60
65
7
8
9
10
11
12
1
2
0
5
10
15
20
15
20
25
30
35
40
45
°C
°C
x
y
x
2
1
Heating
2
Cooling
x
Outdoor temperature
Y
Water temperature
x
x
y
y
1
2
0
5
10
15
20
15
20
25
30
35
40
45
par 4
1
2
3
4
15
25
35
45
55
65
-15
-10
-5
0
5
10
15
20
25
par 4
1
2
3
4
1 - MAX W T° W1
(Par No 121)
2 - NO HEAT T° W1 (Par No 120)
3 - REGION T° O
(Par No 118)
4 - STOP H T° O
(Par No 119)
1 - MAX COOL W T° (Par No 125)
2 - MIN COOL W T° (Par No 124)
3 - COOL STOP T°
(Par No 123)
4 - MAX REGION T° (Par No 122)
Customised climate curves
Parameters 112 and 117 set to zero allow to include a customised curve
in the control.
The pictures show which parameters in the installer configuration table must
be set to create the customised climate curves for heating and cooling.
In the event that the application requests to work at a fixed water set point it
is necessary to set a horizontal climate curve. This is possible by fixing the
parameter 120 = 121 in heating mode and 124 = 125 in cooling mode.
30