19
TECHNICAL ASSISTANCE SERVICE
TECHNICAL ASSISTANCE SERVICE
20
TROUBLESHOOTINg
SUPPLEMENTARY HEATING CIRCUIT
FAULT
CAUSE
SOLUTION
The buffer tank functions incorrectly or
irregularly
Flow rate too high
− Fit a pressure limiter
− Fit a flow reducer
There are blockages or deposits in the
domestic hot water circuit
− Check and clean as necessary
The pump is malfunctioning
− Check the pump
The water temperature from the boiler is
too low
− Check the temperature setting
There is air in the primary circuit
− Bleed the circuit
SOLAR COLLECTOR CIRCUIT
FAULT
CAUSE
SOLUTION
The buffer tank functions incorrectly or
irregularly
There is air in the circuit
− Bleed the circuit
The flow rate is too low or too high
− Check the flow rate of the collector
circuit
Pressure is too low
− Check that circuit pressure is
approximately 3 bar when cold
There is lime scale or sludge in the
cylinder
− Check and clean as necessary
The storage cylinder loses a lot of heat
overnight
There is natural circulation to the
collectors
− Make sure that the non-return valve is
efficient and closes properly. Replace if
necessary
Содержание 7200 Kombi Plus
Страница 1: ...cod 20090482 rev 1 08 2015 7200 Kombi Plus EN INSTALLATION OPERATION AND MAINTENANCE MANUAL...
Страница 21: ...21 END USER END USER...
Страница 22: ...22 END USER END USER...
Страница 23: ...23 END USER END USER...