16
INSTALLER
INSTALLER
Adjust the feet to ensure that the storage cylinder is perfectly
level.
17
9
Wear suitable personal protective equipment and use
suitable safety devices.
0
Do not dispose of packaging material into the environment,
or leave it within the reach of children, since it can become
a potential hazard. Dispose of packaging material in
compliance with applicable legislation.
12
PLACE OF INSTALLATION
R
7200 Kombi Plus
combination storage cylinders can be
installed in any room where there is no specific requirement for
an electrical protection rating higher than IP X0D.
≥ 0,4 m
≥ 0,6 m
≥ 0,3 m
≥ 0,4 m
9
Respect the minimum specified installation distances to
ensure correct installation and access for maintenance.
13
INSTALLATION IN OLDER SYSTEMS AND SYSTEMS
REQUIRINg MODERNISATION
When installing
R
7200 Kombi Plus
combination storage
cylinders in old systems or systems requiring modernisation,
always perform the following checks.
− Make sure that the system is fitted with safety and
control devices in accordance with applicable legislation
and standards
− Make sure that the central heating circuit has been
flushed out to remove all sludge and lime scale, and has
been vented and seal tested
− Make sure that a suitable water treatment system is
installed if the quality of the supply/recirculation water
so demands (refer to the reference values listed in the
table alongside).
REFERENCE VALUES
pH
6-8
Electrical conductivity
less than 200 μS/cm (25°C)
Chlorine ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 0.3 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 35°F
Sulphur ions
none
Ammonia ions
none
Silicon ions
less than 30 ppm