OPERATING FAULT DIAGNOSTICS
The control box has a self-diagnostic system, which easily allows identifying the operating faults (
RED LED
signal). To use this function, wait at least ten seconds from the safety lock out, and then press the reset but-
ton for a minimum of 3 seconds. After releasing the button, the RED LED starts flashing as shown in the dia-
gram below.
The LED gives of a blink code every 3 seconds.
The blink codes give the information about the possible faults, as follows:
Tab. C
BLINK CODE
POSSIBLE CAUSE
2
blinks
The flame does not stabilize at the end of the safety time:
– faulty or soiled ionization probe;
– faulty or soiled fuel valves;
– neutral/phase exchange;
– poor burner regulation.
3
blinks
Minimum air pressure switch does not close:
– air pressure switch faulty;
– air pressure switch incorrectly regulated;
– fan motor does not run.
4
blinks
Extraneous light during pre-purging, or control box faulty.
5
blinks
Minimum air pressure switch does not open:
– air pressure switch faulty;
– air pressure switch incorrectly adjusted.
7
blinks
Loss of flame during operation:
– poor burner regulation;
– faulty or soiled fuel valves;
– short circuit between ionization probe and earth.
10
blinks
Control box faulty.
Press reset
for
>
3s
interval
Blink code
Blink code
RED LED on
wait at least
10s
3s