Faults - Probable causes - Solutions
Tab. P
*1) The system will be restarted not before the condition of the fault is
eliminated (i.e. the dropped safety interlock chain (SIC) or the low
voltage).
806
0
0
Implausible channel set point of the main controller
C
set point
po
actual val-
ue + pro-
gramming
tolerance
807
1
1
Time out of LSB message (message no. = parameter)
Possible cause of error:
–
connection between VSM/LCM GND and protective earth PE
–
acknowledgment of speed change too fast / fault of VSM
–
error at LSB (red LED flashes or is permanently ON)
889
0
0
The gap between two remote fault releases is too short
EN 14459 allows only 4 remote fault resets every 15 min.
Fault release is monitored by remote control software, LAMTEC
SYSTEM BUS and field bus. Exceeding the number of fault releas-
es causes the fault shot-down H889 and further remote fault releas-
es are ignored.
After a delay time another remote fault release is possible.
The fault shut-down H889 also occurs, if fault release is sent with-
out any reason. A reset by terminal is always possible.
How to reset this fault:
–
wait for 15 minutes until you try to reset the fault again
–
cut off the power supply from BT300 for a moment, reconnect it
and reset the fault subsequently.
921
0
0
Relay driver self-test: output oil valve defect
922
0
0
Relay driver self-test: output ignition transformer defect
923
0
0
Relay driver self-test: output gas valve 1 defect
924
0
0
Relay driver self-test: output gas valve 2 defect
925
0
0
Relay driver self-test: output ignition transformer defect
928
0
0
Relay driver self-test: output terminal 41 for oil pump defective
929
0
0
Relay driver self-test: output fan defect
985
0
0
VSM diagnosis error
Possible cause of error:
BurnerTronic expects a VSM module but the exchange of diagnosis
data with the module fails
986
0
0
Dynamic range test recognizes an invalid feedback
Channel
Actual
value
987
0
0
Change-over during staged operation takes too much time
988
0
0
Fuel selection relay in the DFM is defective or inconsistent feed-
back from DFM
989
0
0
Plausibility test of actuator feedback in programmed curve failed
990
Optional
*1)
3
Power failure
996
0
0
Secure parameter writing could not be finished.
Device is blocked
999
Contact the Aftersales Service
Fault
code
TRD
P301=0
P328>0
EN67
P301=2
P328>0
Description D1
D2
Содержание 20171510
Страница 2: ...Original instructions...
Страница 51: ...49 20171652 GB Appendix Electrical panel layout 0 1 1 1 1 2 3 4 3 3 4 3 5 2 6 6 6 7 6 8 6 6 6 6 6 6 6 6 6 6 7 6...
Страница 52: ...20171652 50 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01...
Страница 53: ...51 20171652 GB Appendix Electrical panel layout...
Страница 54: ...20171652 52 GB Appendix Electrical panel layout 0 1 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2...
Страница 55: ...53 20171652 GB Appendix Electrical panel layout 0 0 0 12 3456 7 12 3456 7...
Страница 56: ...20171652 54 GB Appendix Electrical panel layout 01 2 30 3 1 2 0 40 20 22 2 3 5 636 078 40 9 025 7 5...